EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Study on Arc Characteristics and Structural Optimization of a 550 kV Environmentally Friendly Gas Circuit Breaker

Nian Tang, Hanyue Zhao, Dongwei Sun

Plasma · 22.06.2026 · 9 (2) · 22

DOI: 10.3390/plasma9020022 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Plasma, online erschienen am 22.06.2026. Verfasst von Nian Tang und 2 weiteren Autor:innen. Die Arbeit nennt 30 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Science and Technology Project of China Southern Power Grid.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

With increasingly stringent restrictions on SF6 greenhouse gas emissions, C4F7N-based gas mixtures have attracted considerable attention as promising alternatives for high-voltage circuit breakers; however, their relatively weaker arc-quenching capability poses significant challenges for interruption chamber design at high voltage levels. In this study, a 3.5% C4F7N/83.5% CO2/13% O2 gas mixture was used as the arc-extinguishing medium in a 550 kV environmentally friendly gas circuit breaker. Based on a magnetohydrodynamic (MHD) model considering PTFE nozzle ablation effects, systematic optimization studies were conducted on key structural parameters of the puffer-type interruption chamber, including the exhaust hole diameter, nozzle throat diameter and length, arcing contact diameter, and downstream expansion angle. Simulations under arcing times of 9.9 ms and 11.4 ms were performed to evaluate chamber pressure, axial temperature, extinction peak voltage, and post-arc conductance characteristics. The results indicate that extending the nozzle throat straight section to 70 mm, enlarging the exhaust hole, and increasing the moving contact radius can effectively enhance pressure buildup, reduce arc-core temperature, and improve dielectric recovery capability. Under the 11.4 ms arcing condition, the optimized structure achieved an extinction peak voltage of 6972.4 V and a G200 value of 0.731 ms, demonstrating substantially improved interruption performance. These findings reveal the synergistic relationship between arcing time and structural parameters and provide theoretical guidance for the engineering design of environmentally friendly high-voltage gas circuit breakers.

Förderung

  • Science and Technology Project of China Southern Power Grid

Zitieren

APA

Tang, N., Zhao, H., & Sun, D. (2026). Study on Arc Characteristics and Structural Optimization of a 550 kV Environmentally Friendly Gas Circuit Breaker. Plasma, 9(2), 22. https://doi.org/10.3390/plasma9020022

Vancouver

Tang N, Zhao H, Sun D. Study on Arc Characteristics and Structural Optimization of a 550 kV Environmentally Friendly Gas Circuit Breaker. Plasma. 2026;9(2):22. doi:10.3390/plasma9020022

BibTeX
@article{Tang2026,
  author = {Tang, Nian and Zhao, Hanyue and Sun, Dongwei},
  title = {Study on Arc Characteristics and Structural Optimization of a 550 kV Environmentally Friendly Gas Circuit Breaker},
  journal = {Plasma},
  year = {2026},
  volume = {9},
  number = {2},
  pages = {22},
  doi = {10.3390/plasma9020022}
}