Kurz gefasst

Fachartikel in der Zeitschrift AIP Advances, online erschienen am 06.11.2026. Verfasst von Wenqiang Yang und 3 weiteren Autor:innen. Die Arbeit nennt 20 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Science and Technology Project of China Electric Power Rearch Institute.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

The interrupting capacity of low-voltage circuit breakers is critical to the safe and reliable operation of power distribution systems. Owing to the complex physics of arc discharge, existing arc models have difficulty accurately characterizing the dynamic evolution of the arc, which complicates arc-stage classification and performance evaluation throughout the interruption process. To address these requirements, an adaptive arc-stage classification method that combines comprehensive steady-state identification with multiple-threshold criteria is proposed for engineering tests on fully assembled low-voltage circuit breakers. An interruption-test platform is developed to acquire terminal voltage and loop current signals without requiring disassembly of the test specimen or alteration of the arc-extinguishing chamber geometry and associated thermal-fluid boundary conditions, thereby enabling noninvasive characterization of the interruption process. The acquired signals are first processed using exponential smoothing, after which a steady-state detection scheme based on sliding-window statistics is applied to automatically identify four stages of the interruption process: the contact separation stage, arc stagnation stage, arc movement stage, and arc extinction stage. On this basis, key characteristic parameters, including arc energy and the Joule integral, are extracted. A probabilistic preassessment model based on the Joule integral is then developed, with confidence intervals used to quantify uncertainty in interruption performance. This model enables the accurate prediction of high-current interrupting capacity using low-current short-circuit test data. Experimental validation demonstrates the accuracy of the proposed method, with the measured values falling within the estimated confidence intervals.

Förderung

  • Science and Technology Project of China Electric Power Rearch Institute

Zitieren

APA

Yang, W., Wu, C., Dai, J., & Jin, J. (2026). Classification and evaluation method for low-voltage circuit breaker breaking characteristics based on arc analysis. AIP Advances, 16(11). https://doi.org/10.1063/5.0346274

Vancouver

Yang W, Wu C, Dai J, Jin J. Classification and evaluation method for low-voltage circuit breaker breaking characteristics based on arc analysis. AIP Advances. 2026;16(11). doi:10.1063/5.0346274

BibTeX
@article{Yang2026,
  author = {Yang, Wenqiang and Wu, Chunjiu and Dai, Jing and Jin, Jianwei},
  title = {Classification and evaluation method for low-voltage circuit breaker breaking characteristics based on arc analysis},
  journal = {AIP Advances},
  year = {2026},
  volume = {16},
  number = {11},
  doi = {10.1063/5.0346274}
}
Kostenlos starten →