An Explicit Transient Rotor Angle Stability Criterion Involving the Fault Location Factor of Doubly Fed Induction Generator Integrated Power Systems

Yuanhan Zhong, Gao Qiu, Junyong Liu, Tingjian Liu, Youbo Liu, Wei Wei

Electronics · 2025-04-09 · 14 (8) · 1526

DOI: 10.3390/electronics14081526 ↗

At a glance

Journal article in Electronics, published online on 2025-04-09. Written by Yuanhan Zhong and 5 co-authors. Cited 2 times so far (Crossref); 20 references. The full text is freely available (open access, CC BY 4.0). Funded by: the National Natural Science Foundation of China.

AbstractDati bibliograficiCiteRelated studies

Abstract (original language)

Current transient stability analysis of power systems with doubly fed induction generators (DFIGs) draws upon the assumption that nodal electromagnetic power equals to zero during the fault period. The omission of electromagnetic power degrades the fidelity of transient stability analysis and renders the analytical impact of fault location on stability indiscernible. To address this limitation, a DFIG-integrated power system-oriented transient stability mechanism analysis method is proposed involving fault location factors. Firstly, a foundational analysis model is established by integrating a simplified DFIG representation with the improved DC power flow corrected by the fault’s instantaneous short-circuit voltage. Secondly, the non-metallic symmetrical short-circuit fault is equivalently treated as a power injection source, and the faulted electromagnetic power of generators is derived. The proposed equivalence is roughly correct, as its faulted energy integral is validated to approximate ground-truth. Lastly, combining the above analytical formulas and extended equal area criterion (EEAC), a time-domain simulation-free explicit transient stability criterion incorporating fault location factor is settled. Simulation results in a double-generator system with DFIG integration confirm that, compared to existing transient stability criterion, the proposed criterion can expand the stability assessable area by approximately 10% while maintaining accuracy.

Funding

  • the National Natural Science Foundation of China

Cite

APA

Zhong, Y., Qiu, G., Liu, J., Liu, T., Liu, Y., & Wei, W. (2025). An Explicit Transient Rotor Angle Stability Criterion Involving the Fault Location Factor of Doubly Fed Induction Generator Integrated Power Systems. Electronics, 14(8), 1526. https://doi.org/10.3390/electronics14081526

Vancouver

Zhong Y, Qiu G, Liu J, Liu T, Liu Y, Wei W. An Explicit Transient Rotor Angle Stability Criterion Involving the Fault Location Factor of Doubly Fed Induction Generator Integrated Power Systems. Electronics. 2025;14(8):1526. doi:10.3390/electronics14081526

BibTeX
@article{Zhong2025,
  author = {Zhong, Yuanhan and Qiu, Gao and Liu, Junyong and Liu, Tingjian and Liu, Youbo and Wei, Wei},
  title = {An Explicit Transient Rotor Angle Stability Criterion Involving the Fault Location Factor of Doubly Fed Induction Generator Integrated Power Systems},
  journal = {Electronics},
  year = {2025},
  volume = {14},
  number = {8},
  pages = {1526},
  doi = {10.3390/electronics14081526}
}
Start for free →