Power Reference Adjustment and Hybrid Current Limiting for Enhanced Control and Transient Stability of Virtual Synchronous Generator Under Voltage Sags
IEEE Access · 2026 · 14 · 97676-97690
DOI: 10.1109/access.2026.3707238 ↗Kurz gefasst
Fachartikel in der Zeitschrift IEEE Access, 2026. Verfasst von Cheng Xiao und 4 weiteren Autor:innen. Die Arbeit nennt 34 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Scientific Research Project of Higher Education Institutions in Hebei Province, Central Government Guides Local Funds for Science and Technology Development, Science and Technology Program Project of the State Administration for Market Regulation.
Abstract (Originalsprache)
Grid voltage sags can induce power angle instability and overcurrent in the virtual synchronous generator (VSG) due to active power imbalances and terminal voltage mismatches. Conventional current-limiting methods degrade voltage-source characteristics, while fixed virtual impedance lacks adaptability to varying fault severities. This paper proposes a coordinated control strategy for the VSG under voltage sag conditions. An adaptive active power reference is introduced into the active power-frequency control loop to mitigate the power imbalance and suppress power angle acceleration. A dynamic reactive power droop is incorporated into the reactive power-voltage control loop to regulate the steady-state fault current. Additionally, an adaptive virtual impedance is applied during transients to suppress current surges. Simulation results demonstrate that the proposed method maintains power angle stability while limiting the transient peak current and steady-state fault current to 1.3 p.u. and 1.2 p.u., respectively. Compared with existing methods, the proposed strategy preserves the voltage-source operation and improves both transient and steady-state performance.
Förderung
- Scientific Research Project of Higher Education Institutions in Hebei Province
- Central Government Guides Local Funds for Science and Technology Development
- Science and Technology Program Project of the State Administration for Market Regulation
Zitieren
APA
Xiao, C., Hu, Y., Liang, S., Song, Y., & Ren, S. (2026). Power Reference Adjustment and Hybrid Current Limiting for Enhanced Control and Transient Stability of Virtual Synchronous Generator Under Voltage Sags. IEEE Access, 14, 97676-97690. https://doi.org/10.1109/access.2026.3707238
Vancouver
Xiao C, Hu Y, Liang S, Song Y, Ren S. Power Reference Adjustment and Hybrid Current Limiting for Enhanced Control and Transient Stability of Virtual Synchronous Generator Under Voltage Sags. IEEE Access. 2026;14:97676-97690. doi:10.1109/access.2026.3707238
BibTeX
@article{Xiao2026,
author = {Xiao, Cheng and Hu, Yiming and Liang, Shuang and Song, Yubin and Ren, Siyuan},
title = {Power Reference Adjustment and Hybrid Current Limiting for Enhanced Control and Transient Stability of Virtual Synchronous Generator Under Voltage Sags},
journal = {IEEE Access},
year = {2026},
volume = {14},
pages = {97676--97690},
doi = {10.1109/access.2026.3707238}
}