Transient Stability of Paralleled Virtual Synchronous Generator and Grid-Following Inverter
IEEE Transactions on Smart Grid · 2023-11 · 14 (6) · 4451-4466
DOI: 10.1109/tsg.2023.3255168 ↗Kurz gefasst
Fachartikel in der Zeitschrift IEEE Transactions on Smart Grid, 2023-11. Verfasst von Si Phu Me und 4 weiteren Autor:innen. Die Arbeit wurde bisher 75-mal zitiert (Crossref) und nennt 32 Literaturangaben. Gefördert von: Commonwealth Scientific and Industrial Research Organisation, Australian Energy Market Operator (AEMO) in implementing Australia’s Global Power System Transformation (G-PST) Research Roadmap.
Abstract (Originalsprache)
The majority of inverter-based resources (IBRs) currently operate as grid-following inverters (GFLIs). However, these inverters exhibit certain stability issues when integrated in low-strength areas of the grid. To enhance the grid strength in a GFLI-dominant area, virtual synchronous generators (VSGs) can be installed. If the VSG and the GFLI are investigated as a paralleled system, despite the benefits brought by the VSG, in some cases, the transient angle instability process, caused by a voltage sag, is accelerated, making the whole system more prone to instability. Therefore, this paper aims to study the transient angle stability of a paralleled VSG-GFLI system via investigating the voltage at a common bus between the two IBRs. Subsequently, a stable region of the voltage angles of the two IBRs is determined. Based on this stable region, the stability margin of the paralleled system can be determined and used to quantitatively evaluate the system stability. Moreover, an additional control loop is proposed to improve the transient stability of the paralleled system in this paper. The proposed controller can adaptively reduce the power set-point of the VSG to avoid a complete failure of the VSG even when no stable equilibrium point exists during a voltage sag. The stability investigation and performance evaluation of the proposed method are conducted in PSCAD/EMTDC and experimentally validated.
Förderung
- Commonwealth Scientific and Industrial Research Organisation
- Australian Energy Market Operator (AEMO) in implementing Australia’s Global Power System Transformation (G-PST) Research Roadmap
Zitieren
APA
Me, S. P., Ravanji, M. H., Mansour, M. Z., Zabihi, S., & Bahrani, B. (2023). Transient Stability of Paralleled Virtual Synchronous Generator and Grid-Following Inverter. IEEE Transactions on Smart Grid, 14(6), 4451-4466. https://doi.org/10.1109/tsg.2023.3255168
Vancouver
Me SP, Ravanji MH, Mansour MZ, Zabihi S, Bahrani B. Transient Stability of Paralleled Virtual Synchronous Generator and Grid-Following Inverter. IEEE Transactions on Smart Grid. 2023;14(6):4451-4466. doi:10.1109/tsg.2023.3255168
BibTeX
@article{Me2023,
author = {Me, Si Phu and Ravanji, Mohammad Hasan and Mansour, Milad Zarif and Zabihi, Sasan and Bahrani, Behrooz},
title = {Transient Stability of Paralleled Virtual Synchronous Generator and Grid-Following Inverter},
journal = {IEEE Transactions on Smart Grid},
year = {2023},
volume = {14},
number = {6},
pages = {4451--4466},
doi = {10.1109/tsg.2023.3255168}
}
EUVIMED