Journal article in AIP Advances, published online on 2026-06-08. Written by Shiwei Tian and 6 co-authors. 23 references. The full text is freely available (open access, CC BY 4.0). Funded by: Central Government Funds for Guiding Local Science and Technology Development—Science and Technology Innovation Base Project.

AbstractBibliografiske oplysningerCiteRelated studies

Abstract (original language)

In electromagnetic-fluid-thermal coupling calculations, conventional numerical methods often face challenges regarding computational accuracy and efficiency. To address the shortcomings of traditional methods under extreme operating conditions, such as over-excitation in ultra-high-voltage transformers, this paper proposes a reduced-order model (ROM) based on proper orthogonal decomposition (POD) and Kriging response surface methods for the rapid calculation of temperature fields under various operating conditions. First, a full-order computational model for electromagnetic-fluid-thermal coupling is established to analyze the nonlinear transfer law of hotspots under over-excitation conditions. Subsequently, a POD-Kriging reduced-order computational model is constructed. The results show that the maximum relative error of the ROM is only 2.92%, the single-step calculation time is shortened to 1.02 s, and the computational efficiency is 8894 times higher than that of the full-order model (FOM). This method significantly improves the calculation speed of the temperature field while ensuring high calculation accuracy.

Funding

  • Central Government Funds for Guiding Local Science and Technology Development—Science and Technology Innovation Base Project

Cite

APA

Tian, S., Gao, F., Dong, Y., Qi, L., Sun, Y., Liu, Y., & Liu, G. (2026). Electromagnetic-fluid-thermal coupling analysis and rapid temperature field calculation of UHV transformers under multiple operating conditions. AIP Advances, 16(6). https://doi.org/10.1063/5.0337340

Vancouver

Tian S, Gao F, Dong Y, Qi L, Sun Y, Liu Y, et al. Electromagnetic-fluid-thermal coupling analysis and rapid temperature field calculation of UHV transformers under multiple operating conditions. AIP Advances. 2026;16(6). doi:10.1063/5.0337340

BibTeX
@article{Tian2026,
  author = {Tian, Shiwei and Gao, Fangyu and Dong, Yufei and Qi, Liuyu and Sun, Youliang and Liu, Yunpeng and Liu, Gang},
  title = {Electromagnetic-fluid-thermal coupling analysis and rapid temperature field calculation of UHV transformers under multiple operating conditions},
  journal = {AIP Advances},
  year = {2026},
  volume = {16},
  number = {6},
  doi = {10.1063/5.0337340}
}
Start for free →