Optimizing Temperature Measurement Points in Dry-Type Transformers of Urban Rail Transit Based on Bidirectionally Coupled Electromagnetic–Thermal–Fluid Model
IEEE Transactions on Instrumentation and Measurement · 2026 · 75 · 9010221-9010221
DOI: 10.1109/tim.2026.3746829 ↗Kurz gefasst
Fachartikel in der Zeitschrift IEEE Transactions on Instrumentation and Measurement, 2026. Verfasst von Xiaojun Sun und 6 weiteren Autor:innen. Die Arbeit nennt 33 Literaturangaben. Gefördert von: National Natural Science Foundation of China, Sichuan Science and Technology Program, China Postdoctoral Science Foundation.
Abstract (Originalsprache)
To address the design of temperature-monitoring networks for dry-type transformers in urban rail transit systems, this article proposes a reconstruction-oriented sensor placement method that improves thermal-field observability under practical installation constraints. First, an electromagnetic–thermal–fluid bidirectionally coupled model is established and experimentally validated to generate temperature fields under diverse operating conditions. Temperature and temperature-gradient information are then converted into dimensionless spatial weights, and proper orthogonal decomposition (POD) combined with Gappy POD is employed to reconstruct the complete field from limited measurements. Accordingly, the weighted reconstruction root-mean-square error (RMSE) and sensor number are minimized simultaneously using a multiobjective genetic algorithm (GA), and a technique for order preference by similarity to ideal solution (TOPSIS)-based procedure selects a compromise solution from the Pareto set. The sensor coverage, which is defined as the proportion of field points reconstructed within a prescribed error tolerance is used to assess the performance of the sensor placement scheme. Under noise-free sensor observations, tests under both regular and extreme conditions show that the recommended sensor configuration achieves 100 % and 97.38 % weighted coverage, respectively, within a $2~^{\circ }$ C tolerance. Compared with the existing scheme, it reduces the weighted RMSE by 93.2 % and 94.4 %, demonstrating the accurate reconstruction of thermally critical regions and effective overall reconstruction ability under severe operating conditions.
Förderung
- National Natural Science Foundation of China
- Sichuan Science and Technology Program
- China Postdoctoral Science Foundation
- China State Railway Group Company Ltd. Science and Technology Research and Development Plan
Zitieren
APA
Sun, X., Yuan, S., Huang, C., Zhao, L., Wang, Q., Lin, S., & He, Z. (2026). Optimizing Temperature Measurement Points in Dry-Type Transformers of Urban Rail Transit Based on Bidirectionally Coupled Electromagnetic–Thermal–Fluid Model. IEEE Transactions on Instrumentation and Measurement, 75, 9010221-9010221. https://doi.org/10.1109/tim.2026.3746829
Vancouver
Sun X, Yuan S, Huang C, Zhao L, Wang Q, Lin S, et al. Optimizing Temperature Measurement Points in Dry-Type Transformers of Urban Rail Transit Based on Bidirectionally Coupled Electromagnetic–Thermal–Fluid Model. IEEE Transactions on Instrumentation and Measurement. 2026;75:9010221-9010221. doi:10.1109/tim.2026.3746829
BibTeX
@article{Sun2026,
author = {Sun, Xiaojun and Yuan, Shuai and Huang, Cheng and Zhao, Liping and Wang, Qi and Lin, Sheng and He, Zhengyou},
title = {Optimizing Temperature Measurement Points in Dry-Type Transformers of Urban Rail Transit Based on Bidirectionally Coupled Electromagnetic–Thermal–Fluid Model},
journal = {IEEE Transactions on Instrumentation and Measurement},
year = {2026},
volume = {75},
pages = {9010221--9010221},
doi = {10.1109/tim.2026.3746829}
}
EUVIMED