Electromagnetic-fluid-thermal coupling analysis and rapid temperature field calculation of UHV transformers under multiple operating conditions
AIP Advances · 01.06.2026 · 16 (6)
DOI: 10.1063/5.0337340 ↗Kurz gefasst
Fachartikel in der Zeitschrift AIP Advances, online erschienen am 08.06.2026. Verfasst von Shiwei Tian und 6 weiteren Autor:innen. Die Arbeit nennt 23 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Central Government Funds for Guiding Local Science and Technology Development—Science and Technology Innovation Base Project.
Abstract (Originalsprache)
In electromagnetic-fluid-thermal coupling calculations, conventional numerical methods often face challenges regarding computational accuracy and efficiency. To address the shortcomings of traditional methods under extreme operating conditions, such as over-excitation in ultra-high-voltage transformers, this paper proposes a reduced-order model (ROM) based on proper orthogonal decomposition (POD) and Kriging response surface methods for the rapid calculation of temperature fields under various operating conditions. First, a full-order computational model for electromagnetic-fluid-thermal coupling is established to analyze the nonlinear transfer law of hotspots under over-excitation conditions. Subsequently, a POD-Kriging reduced-order computational model is constructed. The results show that the maximum relative error of the ROM is only 2.92%, the single-step calculation time is shortened to 1.02 s, and the computational efficiency is 8894 times higher than that of the full-order model (FOM). This method significantly improves the calculation speed of the temperature field while ensuring high calculation accuracy.
Förderung
- Central Government Funds for Guiding Local Science and Technology Development—Science and Technology Innovation Base Project
Zitieren
APA
Tian, S., Gao, F., Dong, Y., Qi, L., Sun, Y., Liu, Y., & Liu, G. (2026). Electromagnetic-fluid-thermal coupling analysis and rapid temperature field calculation of UHV transformers under multiple operating conditions. AIP Advances, 16(6). https://doi.org/10.1063/5.0337340
Vancouver
Tian S, Gao F, Dong Y, Qi L, Sun Y, Liu Y, et al. Electromagnetic-fluid-thermal coupling analysis and rapid temperature field calculation of UHV transformers under multiple operating conditions. AIP Advances. 2026;16(6). doi:10.1063/5.0337340
BibTeX
@article{Tian2026,
author = {Tian, Shiwei and Gao, Fangyu and Dong, Yufei and Qi, Liuyu and Sun, Youliang and Liu, Yunpeng and Liu, Gang},
title = {Electromagnetic-fluid-thermal coupling analysis and rapid temperature field calculation of UHV transformers under multiple operating conditions},
journal = {AIP Advances},
year = {2026},
volume = {16},
number = {6},
doi = {10.1063/5.0337340}
}
EUVIMED