Numerical Assessment of Smoke Flow and Life Safety in a Subway Station Fire

Byongyoun Hwang, Kyubin Lee, Hun Heo, Taehoon Kim, Seungun Chae

Journal of the Korean Society of Hazard Mitigation · 30.04.2026 · 26 (2) · 115-124

DOI: 10.9798/kosham.2026.26.2.115 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Journal of the Korean Society of Hazard Mitigation, erschienen am 30.04.2026. Verfasst von Byongyoun Hwang und 4 weiteren Autor:innen. Die Arbeit nennt 13 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY-NC 4.0). Gefördert von: Ministry of Land, Infrastructure and Transport, Korea Agency for Infrastructure Technology Advancement.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

This study developed a three-dimensional numerical model of an actual subway station using PyroSim and evaluated smoke movement and life safety during fire scenarios through Fire Dynamics Simulator (FDS) simulations. A mesh sensitivity analysis was conducted to determine the appropriate mesh resolution, and the effects of smoke and ventilation system operation on smoke spread and life safety criteria were examined. The results showed that activating the system increased the available safe egress time (ASET) based on visibility from 208.5 s to 330.1 s, indicating improved evacuation feasibility. Temperature and toxic gas concentrations remained within acceptable limits during system operation. These findings demonstrate that smoke and ventilation systems play a critical role in enhancing the fire-safety performance of underground subway stations and provide foundational data for performance-based design and fire-safety strategies in underground structures.

Förderung

  • Ministry of Land, Infrastructure and Transport
  • Korea Agency for Infrastructure Technology Advancement

Zitieren

APA

Hwang, B., Lee, K., Heo, H., Kim, T., & Chae, S. (2026). Numerical Assessment of Smoke Flow and Life Safety in a Subway Station Fire. Journal of the Korean Society of Hazard Mitigation, 26(2), 115-124. https://doi.org/10.9798/kosham.2026.26.2.115

Vancouver

Hwang B, Lee K, Heo H, Kim T, Chae S. Numerical Assessment of Smoke Flow and Life Safety in a Subway Station Fire. Journal of the Korean Society of Hazard Mitigation. 2026;26(2):115-124. doi:10.9798/kosham.2026.26.2.115

BibTeX
@article{Hwang2026,
  author = {Hwang, Byongyoun and Lee, Kyubin and Heo, Hun and Kim, Taehoon and Chae, Seungun},
  title = {Numerical Assessment of Smoke Flow and Life Safety in a Subway Station Fire},
  journal = {Journal of the Korean Society of Hazard Mitigation},
  year = {2026},
  volume = {26},
  number = {2},
  pages = {115--124},
  doi = {10.9798/kosham.2026.26.2.115}
}