Optimization of Near-Source Concentrated Smoke Exhaust in Long Subway Station Entrance Passageways Under Concourse Fire Conditions
Processes · 10.06.2026 · 14 (12) · 1878
DOI: 10.3390/pr14121878 ↗Kurz gefasst
Fachartikel in der Zeitschrift Processes, online erschienen am 10.06.2026. Verfasst von Bo Lan und 3 weiteren Autor:innen. Die Arbeit nennt 25 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Chongqing Municipal Education Commission, Chongqing Industry Polytechnic University.
Abstract (Originalsprache)
Smoke spread from concourse fires into long entrance passageways can threaten evacuation in deep-buried subway stations, especially when smoke moves upward along inclined escalator sections. This study used a 1:8-scale Fire Dynamics Simulator model to investigate smoke control in a concourse connected to two long entrance passageways. Concourse-only smoke exhaust, conventional combined smoke exhaust, different passageway vent configurations, and an optimized near-source concentrated arrangement were compared. The baseline concourse extraction rate failed to prevent smoke from entering the passageways. At a heat release rate of 15.55 kW, smoke was nearly prevented from entering landing I only when the concourse extraction rate was increased to six times the baseline value. Under conventional combined exhaust, the passageway extraction capacity was distributed between landing I and landing II, but smoke still entered escalator section I. When the total extraction rate of each single-side passageway was unchanged, concentrating the extraction capacity at landing I allowed smoke to be extracted before entering escalator section I. The optimized arrangement prevented smoke from entering escalator section I under both centered and right-offset fire source conditions for the tested passageway geometry, heat release rate, and extraction-rate conditions.
Förderung
- Chongqing Municipal Education Commission
- Chongqing Industry Polytechnic University
Zitieren
APA
Lan, B., Zhang, T., Shen, T., & Xiao, Z. (2026). Optimization of Near-Source Concentrated Smoke Exhaust in Long Subway Station Entrance Passageways Under Concourse Fire Conditions. Processes, 14(12), 1878. https://doi.org/10.3390/pr14121878
Vancouver
Lan B, Zhang T, Shen T, Xiao Z. Optimization of Near-Source Concentrated Smoke Exhaust in Long Subway Station Entrance Passageways Under Concourse Fire Conditions. Processes. 2026;14(12):1878. doi:10.3390/pr14121878
BibTeX
@article{Lan2026,
author = {Lan, Bo and Zhang, Tao and Shen, Ting and Xiao, Zheng},
title = {Optimization of Near-Source Concentrated Smoke Exhaust in Long Subway Station Entrance Passageways Under Concourse Fire Conditions},
journal = {Processes},
year = {2026},
volume = {14},
number = {12},
pages = {1878},
doi = {10.3390/pr14121878}
}
EUVIMED