Kurz gefasst

Fachartikel in der Zeitschrift Fire Science and Engineering, erschienen am 30.04.2026. Verfasst von Jihee Lee und 3 weiteren Autor:innen. Die Arbeit nennt 18 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY-NC 4.0). Gefördert von: Ministry of Climate, Energy and Environment, Korea Energy Technology Evaluation and Planning.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

This study compared the fire suppression performance of gas-based automatic extinguishing systems (HFC-125 and FK-5-1-12) and a water mist system for localized cabinet fires in nuclear power plants. Fire tests using n-heptane and diesel were conducted under simulated cabinet fire conditions, and the suppression performance was evaluated based on the activation temperature, extinguishing time, and reignition behavior. The gas-based systems extinguished fires within 11~17 s, whereas the water mist system achieved a comparable performance with extinguishing times of 15~18 s. No reignition was observed in any test case. These findings indicate that the water mist system is a feasible alternative for localized cabinet fire suppression, offering reduced dependency on enclosure conditions compared with gas-based systems.

Förderung

  • Ministry of Climate, Energy and Environment
  • Korea Energy Technology Evaluation and Planning

Zitieren

APA

Lee, J., Kwon, H., Jung, S., & Park, S. (2026). Comparative Study on the Fire Suppression Performance of Water Mist Systems and Gas-Based Automatic Extinguishing Devices under Nuclear Power Plant Cabinet Fire Conditions. Fire Science and Engineering, 40(2), 26-36. https://doi.org/10.7731/kifse.ad868c89

Vancouver

Lee J, Kwon H, Jung S, Park S. Comparative Study on the Fire Suppression Performance of Water Mist Systems and Gas-Based Automatic Extinguishing Devices under Nuclear Power Plant Cabinet Fire Conditions. Fire Science and Engineering. 2026;40(2):26-36. doi:10.7731/kifse.ad868c89

BibTeX
@article{Lee2026,
  author = {Lee, Jihee and Kwon, Heejun and Jung, Seok and Park, Sehun},
  title = {Comparative Study on the Fire Suppression Performance of Water Mist Systems and Gas-Based Automatic Extinguishing Devices under Nuclear Power Plant Cabinet Fire Conditions},
  journal = {Fire Science and Engineering},
  year = {2026},
  volume = {40},
  number = {2},
  pages = {26--36},
  doi = {10.7731/kifse.ad868c89}
}
Kostenlos starten →