Full-Scale Experimental Evaluation of Fire-Spread Prevention Performance of Vertical Fire-Barrier Screen Combined with Sprinkler Systems in Underground Parking Garages
Fire Science and Engineering · 31.10.2026 · 40 (5) · 19-29
DOI: 10.7731/kifse.7da8e542 ↗Kurz gefasst
Fachartikel in der Zeitschrift Fire Science and Engineering, erschienen am 31.10.2026. Verfasst von Seoung-Kwon Lee und 3 weiteren Autor:innen. Die Arbeit nennt 17 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY-NC 4.0). Gefördert von: Ministry of Land, Infrastructure and Transport, National Fire Agency, National Research Foundation of Korea.
Abstract (Originalsprache)
This study evaluated the fire-spread prevention performance of a vertical fire barrier integrated with a sprinkler system through full-scale EV fire tests in an underground parking garage mockup. Two configurations—a barrier-only system and a barrier–sprinkler system—were compared. Although thermal runaway occurred in all battery modules under both conditions, the integrated system formed a continuous water film on the barrier surface, thus limiting the adjacent vehicle temperature to below 40 °C and preventing fire spread. By contrast, the barrier-only condition allowed flame propagation through the ceiling clearance, thereby increasing the adjacent vehicle temperature to 768 °C and causing fire spread. These results demonstrate that integrating a vertical fire barrier with a sprinkler system effectively suppresses early-stage fire spread and provides additional time for firefighting.
Förderung
- Ministry of Land, Infrastructure and Transport
- National Fire Agency
- National Research Foundation of Korea
Zitieren
APA
Lee, S., Lee, S., Kim, J., & Kim, T. (2026). Full-Scale Experimental Evaluation of Fire-Spread Prevention Performance of Vertical Fire-Barrier Screen Combined with Sprinkler Systems in Underground Parking Garages. Fire Science and Engineering, 40(5), 19-29. https://doi.org/10.7731/kifse.7da8e542
Vancouver
Lee S, Lee S, Kim J, Kim T. Full-Scale Experimental Evaluation of Fire-Spread Prevention Performance of Vertical Fire-Barrier Screen Combined with Sprinkler Systems in Underground Parking Garages. Fire Science and Engineering. 2026;40(5):19-29. doi:10.7731/kifse.7da8e542
BibTeX
@article{Lee2026,
author = {Lee, Seoung-Kwon and Lee, Su-Haeng and Kim, Jung-Yong and Kim, Tae-Jung},
title = {Full-Scale Experimental Evaluation of Fire-Spread Prevention Performance of Vertical Fire-Barrier Screen Combined with Sprinkler Systems in Underground Parking Garages},
journal = {Fire Science and Engineering},
year = {2026},
volume = {40},
number = {5},
pages = {19--29},
doi = {10.7731/kifse.7da8e542}
}
EUVIMED