EUVIMEDEUVIMED entdecken
Open Access · CC BY-NC 4.0

Full-Scale Experimental Evaluation of Fire-Spread Prevention Performance of Vertical Fire-Barrier Screen Combined with Sprinkler Systems in Underground Parking Garages

Seoung-Kwon Lee, Su-Haeng Lee, Jung-Yong Kim, Tae-Jung Kim

Fire Science and Engineering · 31.10.2026 · 40 (5) · 19-29

DOI: 10.7731/kifse.7da8e542 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Fire Science and Engineering, erschienen am 31.10.2026. Verfasst von Seoung-Kwon Lee und 3 weiteren Autor:innen. Die Arbeit nennt 17 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY-NC 4.0). Gefördert von: Ministry of Land, Infrastructure and Transport, National Fire Agency, National Research Foundation of Korea.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

This study evaluated the fire-spread prevention performance of a vertical fire barrier integrated with a sprinkler system through full-scale EV fire tests in an underground parking garage mockup. Two configurations—a barrier-only system and a barrier–sprinkler system—were compared. Although thermal runaway occurred in all battery modules under both conditions, the integrated system formed a continuous water film on the barrier surface, thus limiting the adjacent vehicle temperature to below 40 °C and preventing fire spread. By contrast, the barrier-only condition allowed flame propagation through the ceiling clearance, thereby increasing the adjacent vehicle temperature to 768 °C and causing fire spread. These results demonstrate that integrating a vertical fire barrier with a sprinkler system effectively suppresses early-stage fire spread and provides additional time for firefighting.

Förderung

  • Ministry of Land, Infrastructure and Transport
  • National Fire Agency
  • National Research Foundation of Korea

Zitieren

APA

Lee, S., Lee, S., Kim, J., & Kim, T. (2026). Full-Scale Experimental Evaluation of Fire-Spread Prevention Performance of Vertical Fire-Barrier Screen Combined with Sprinkler Systems in Underground Parking Garages. Fire Science and Engineering, 40(5), 19-29. https://doi.org/10.7731/kifse.7da8e542

Vancouver

Lee S, Lee S, Kim J, Kim T. Full-Scale Experimental Evaluation of Fire-Spread Prevention Performance of Vertical Fire-Barrier Screen Combined with Sprinkler Systems in Underground Parking Garages. Fire Science and Engineering. 2026;40(5):19-29. doi:10.7731/kifse.7da8e542

BibTeX
@article{Lee2026,
  author = {Lee, Seoung-Kwon and Lee, Su-Haeng and Kim, Jung-Yong and Kim, Tae-Jung},
  title = {Full-Scale Experimental Evaluation of Fire-Spread Prevention Performance of Vertical Fire-Barrier Screen Combined with Sprinkler Systems in Underground Parking Garages},
  journal = {Fire Science and Engineering},
  year = {2026},
  volume = {40},
  number = {5},
  pages = {19--29},
  doi = {10.7731/kifse.7da8e542}
}
Kostenlos starten →