Experimental Study on the Effectiveness of Sprinkler Installation Requirements for Mitigating Fire Spread between Fire Compartments
Fire Science and Engineering · 31.08.2026 · 40 (4) · 102-110
DOI: 10.7731/kifse.0d626d5f ↗Kurz gefasst
Fachartikel in der Zeitschrift Fire Science and Engineering, erschienen am 31.08.2026. Verfasst von Ho-Sik Han und 2 weiteren Autor:innen. Die Arbeit wurde bisher 1-mal zitiert (Crossref) und nennt 19 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY-NC 4.0). Gefördert von: Ministry of Land, Infrastructure and Transport, Korea Agency for Infrastructure Technology Advancement.
Abstract (Originalsprache)
This study investigated the effectiveness of sprinklers installed around an opening in mitigating the spread of fire between fire compartments. Full-scale fire experiments were conducted using a compartment based on the ISO 9705-1 room geometry. Three experimental configurations were evaluated: an unprotected opening (UO), an opening with a top sprinkler (OTS), and an opening with four-side sprinklers (OFSS). A propane burner was operated at heat release rates of 0.5, 1.0, 1.5, and 2.5 MW, and flame behavior and heat flux outside the opening were measured. Under the UO condition, the flame and high-temperature regions expanded as the heat release rate increased, and flame ejection through the opening was observed at 2.5 MW. The average heat flux attenuation ranged from approximately 30% to 45% for the OTS configuration and from 52% to 76% for the OFSS configuration. These results indicate that sprinklers installed around an opening can reduce external thermal exposure, with greater mitigation achieved when sprinklers are installed on all four sides of the opening.
Förderung
- Ministry of Land, Infrastructure and Transport
- Korea Agency for Infrastructure Technology Advancement
Zitieren
APA
Han, H., Yun, H., & Cho, G. (2026). Experimental Study on the Effectiveness of Sprinkler Installation Requirements for Mitigating Fire Spread between Fire Compartments. Fire Science and Engineering, 40(4), 102-110. https://doi.org/10.7731/kifse.0d626d5f
Vancouver
Han H, Yun H, Cho G. Experimental Study on the Effectiveness of Sprinkler Installation Requirements for Mitigating Fire Spread between Fire Compartments. Fire Science and Engineering. 2026;40(4):102-110. doi:10.7731/kifse.0d626d5f
BibTeX
@article{Han2026,
author = {Han, Ho-Sik and Yun, Hong-Seok and Cho, Gyu-Hwan},
title = {Experimental Study on the Effectiveness of Sprinkler Installation Requirements for Mitigating Fire Spread between Fire Compartments},
journal = {Fire Science and Engineering},
year = {2026},
volume = {40},
number = {4},
pages = {102--110},
doi = {10.7731/kifse.0d626d5f}
}
EUVIMED