ANALYSIS OF THE STRUCTURAL INTEGRITY OF A FUEL TANK DUE TO BUCKLING USING THE FINITE ELEMENT METHOD
TOPLAMA · 30.05.2026 · 3 (3) · 82-93
DOI: 10.61397/tla.v3i3.503 ↗Kurz gefasst
Fachartikel in der Zeitschrift TOPLAMA, online erschienen am 30.05.2026. Verfasst von Hendri Septian und 1 weiteren Autor:innen. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).
Abstract (Originalsprache)
Storage tanks for fuel oil are commonly used in the oil, gas, and petrochemical industries. These tanks typically have thin-walled structures that are susceptible to buckling under excessive pressure. A hydrostatic test is required to determine the structural strength of the tank and to check for any leaks or cracks in the shell course. During the hydrostatic test, special attention must be given to the dewatering process to avoid excessive pressure differences inside and outside the tank that could lead to buckling. In this study, the tank experienced buckling in the shell course due to errors during the dewatering process, resulting in out-of-roundness in the affected shell course that exceeded the API 650 standard, with a maximum deviation of ±25 mm (from 45 m to
Zitieren
APA
Septian, H., & Perkasa, M. (2026). ANALYSIS OF THE STRUCTURAL INTEGRITY OF A FUEL TANK DUE TO BUCKLING USING THE FINITE ELEMENT METHOD. TOPLAMA, 3(3), 82-93. https://doi.org/10.61397/tla.v3i3.503
Vancouver
Septian H, Perkasa M. ANALYSIS OF THE STRUCTURAL INTEGRITY OF A FUEL TANK DUE TO BUCKLING USING THE FINITE ELEMENT METHOD. TOPLAMA. 2026;3(3):82-93. doi:10.61397/tla.v3i3.503
BibTeX
@article{Septian2026,
author = {Septian, Hendri and Perkasa, Mustasyar},
title = {ANALYSIS OF THE STRUCTURAL INTEGRITY OF A FUEL TANK DUE TO BUCKLING USING THE FINITE ELEMENT METHOD},
journal = {TOPLAMA},
year = {2026},
volume = {3},
number = {3},
pages = {82--93},
doi = {10.61397/tla.v3i3.503}
}
EUVIMED