EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Experimental Study of the Electrical and Physiochemical Properties of Different Types of Crude Palm Oils as Dielectric Insulating Fluids in Transformers

Pichai Muangpratoom, Chinnapat Suriyasakulpong, Sakda Maneerot, Wanwilai Vittayakorn, Norasage Pattanadech

Sustainability · 27.09.2023 · 15 (19) · 14269

DOI: 10.3390/su151914269 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Sustainability, online erschienen am 27.09.2023. Verfasst von Pichai Muangpratoom und 4 weiteren Autor:innen. Die Arbeit wurde bisher 10-mal zitiert (Crossref) und nennt 56 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Rajamangala University of Technology Isan.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

This paper gives information on the electrical and physiochemical characteristics of six different types of palm oil compared with traditional mineral oil. We found that natural processed crude palm oil (PO-C) had a higher resistance to AC breakdown voltage than other types of palm oil, including traditional mineral oil. The results of the positive lightning impulse voltage test for PO-C were still the highest compared to other types of palm oil, including traditional mineral oil, at 58.26%. The summarised dissipation factors of all tested crude palm oils were significantly higher than those of mineral oils, which will make the palm oil less insulating, especially in PO-A palm oil (36.197%), where the values were higher than those of other oils, while mineral oil has a slightly increased dispersion factor. For relative permittivity, all palm oils were compared, and it was found that PO-C had a lower relative permittivity than the other oils. In terms of physical and chemical properties, in the moisture content test on all oils, PO-C had the percentile with the highest moisture content decrease of 58.74%. In the case of testing the surface tension value, it was found that traditional mineral oil had the highest value (48.46 m/Nm) when compared to palm oil. On the other hand, the acidity in traditional mineral oil is the lowest (0.03 mg KOH/g) compared to all palm oils. Results from studies demonstrate the possibility of using natural processed crude palm oil, or PO-C, as a replacement for traditional mineral oil. This is consistent with the results of electrical properties that show PO-C is higher than other types of palm oil and includes traditional mineral oil.

Förderung

  • Rajamangala University of Technology Isan

Zitieren

APA

Muangpratoom, P., Suriyasakulpong, C., Maneerot, S., Vittayakorn, W., & Pattanadech, N. (2023). Experimental Study of the Electrical and Physiochemical Properties of Different Types of Crude Palm Oils as Dielectric Insulating Fluids in Transformers. Sustainability, 15(19), 14269. https://doi.org/10.3390/su151914269

Vancouver

Muangpratoom P, Suriyasakulpong C, Maneerot S, Vittayakorn W, Pattanadech N. Experimental Study of the Electrical and Physiochemical Properties of Different Types of Crude Palm Oils as Dielectric Insulating Fluids in Transformers. Sustainability. 2023;15(19):14269. doi:10.3390/su151914269

BibTeX
@article{Muangpratoom2023,
  author = {Muangpratoom, Pichai and Suriyasakulpong, Chinnapat and Maneerot, Sakda and Vittayakorn, Wanwilai and Pattanadech, Norasage},
  title = {Experimental Study of the Electrical and Physiochemical Properties of Different Types of Crude Palm Oils as Dielectric Insulating Fluids in Transformers},
  journal = {Sustainability},
  year = {2023},
  volume = {15},
  number = {19},
  pages = {14269},
  doi = {10.3390/su151914269}
}
Kostenlos starten →