EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

An Evaluation Method for Partial Discharge in Generator Stator Bar Insulation Based on Fiber-Optic Acoustic Detection

Jianlin Hu iD, Jiapeng Yang iD, Peiyu Qin, Xingliang Jiang, Wentao Luo iD

Sensors · 25.03.2026 · 26 (7) · 2053

DOI: 10.3390/s26072053 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Sensors, online erschienen am 25.03.2026. Verfasst von Jianlin Hu und 4 weiteren Autor:innen. Beteiligte Einrichtung: School of Electrical Engineering, Chongqing University, Chongqing 400044, China. Die Arbeit nennt 31 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).

AbstractSchlagwörterBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Partial-discharge (PD) monitoring is essential for assessing the insulation condition of generator stator bars. Conventional methods are susceptible to electromagnetic interference and are difficult to deploy in confined stator geometries. Fiber-optic acoustic detection technology offers strong immunity to electromagnetic interference and is suitable for the narrow and high-interference environment of stator bars, but it cannot directly provide discharge magnitude information. Therefore, in this study, fiber-optic acoustic detection technology was employed to acquire partial discharge acoustic signals from stator bars, and a mandrel-type fiber-optic acoustic sensor was developed, with PD tests performed on full-scale stator bars with internal defects. Meanwhile, considering the complex temporal characteristics of PD acoustic signals, a hybrid neural network—Transformer–convolutional neural network–long short-term memory (Transformer–CNN–LSTM)—was constructed for long-term time-series modeling to establish the mapping between acoustic signals and discharge magnitude intervals. The results indicate that fiber-optic acoustic detection enables sensitive and stable detection of weak PD acoustic signals. Phase-resolved PD (PRPD) patterns from the proposed system align with the discharge characteristics of internal defects, with the acoustic signal showing a phase lag relative to the electrical PD signal. The hybrid model achieved an overall interval estimation accuracy of 96.6%, outperforming CNN and CNN-LSTM models, with accuracies of 100% and 99.4% for discharge magnitude intervals below 100 pC and above 2000 pC, respectively.

Schlagwörter

Stichwörter der Autor:innen

fiber-optic acoustic detectiongenerator stator barlong time-series modelingpartial discharge

Autor:innen und Institutionen

  • School of Electrical Engineering, Chongqing University, Chongqing 400044, China.

ORCID-Profile: Jianlin Hu, Jiapeng Yang, Wentao Luo

Zitieren

APA

Hu, J., Yang, J., Qin, P., Jiang, X., & Luo, W. (2026). An Evaluation Method for Partial Discharge in Generator Stator Bar Insulation Based on Fiber-Optic Acoustic Detection. Sensors, 26(7), 2053. https://doi.org/10.3390/s26072053

Vancouver

Hu J, Yang J, Qin P, Jiang X, Luo W. An Evaluation Method for Partial Discharge in Generator Stator Bar Insulation Based on Fiber-Optic Acoustic Detection. Sensors. 2026;26(7):2053. doi:10.3390/s26072053

BibTeX
@article{Hu2026,
  author = {Hu, Jianlin and Yang, Jiapeng and Qin, Peiyu and Jiang, Xingliang and Luo, Wentao},
  title = {An Evaluation Method for Partial Discharge in Generator Stator Bar Insulation Based on Fiber-Optic Acoustic Detection},
  journal = {Sensors},
  year = {2026},
  volume = {26},
  number = {7},
  pages = {2053},
  doi = {10.3390/s26072053}
}
Kostenlos starten →