EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Design and Implementation of a Cascade Control System for a Variable Air Volume in Operating Rooms Based on Pressure and Temperature Feedback

Abdulmohaymin Bassim Qassim iD, Shaimaa Mudhafar Hashim iD, Wajdi Sadik Aboud iD

Sensors · 2025

DOI: 10.3390/s25185656 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Sensors, 2025. Verfasst von Abdulmohaymin Bassim Qassim und 2 weiteren Autor:innen. Beteiligte Einrichtung: Department of Artificial Intelligence & Robotics Engineering, Al-Nahrain University, P.O. Box 64040, Al Jadriyah, Baghdad 10072, Iraq. Hauptthemen laut MEDLINE: Operating Rooms. Die Arbeit wurde bisher 2-mal zitiert (Crossref) und nennt 26 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).

AbstractSchlagwörterBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

This research presents the design and implementation of a cascade Proportional–Integral (PI) controller tailored for a Variable Air Volume (VAV) system that was specially created and executed particularly for hospital operating rooms. The main goal of this work is to make sure that the temperature and positive pressure stay within the limits set by ASHRAE Standard 170-2017. This is necessary for patient safety, surgical accuracy, and system reliability. The proposed cascade design uses dual-loop PI controllers: one loop controls the temperature based on user-defined setpoints by local control touch screen, and the other loop accurately modulates the differential pressure to keep the pressure of the environment sterile (positive pressure). The system works perfectly with Building Automation System (BAS) parts from Automated Logic Corporation (ALC) brand, like Direct Digital Controllers (DDC) and Web-CTRL software with Variable Frequency Drives (VFDs), advanced sensors, and actuators that give real-time feedback, precise control, and energy efficiency. The system’s exceptional responsiveness, extraordinary stability, and resilient flexibility were proven through empirical validation at the Korean Iraqi Critical Care Hospital in Baghdad under a variety of operating circumstances. Even during rapid load changes and door openings, the control system successfully maintained the temperature between 18 and 22 °C and the differential pressure between 3 and 15 Pascals. Four performance scenarios, such as normal (pressure and temperature), high-temperature, high-pressure, and low-pressure cases, were tested. The results showed that the cascade PI control strategy is a reliable solution for critical care settings because it achieves precise environmental control, improves energy efficiency, and ensures compliance with strict healthcare facility standards.

Schlagwörter

MeSH-Schlagwörter (MEDLINE)

Operating RoomsTemperatureHumansPressureFeedbackEquipment Design

Stichwörter der Autor:innen

VAV air-conditioning systemsautomated logic corporationbuilding automation systemcascade control systemdirect digital controllertemperature and pressure control of operating rooms

Autor:innen und Institutionen

  • Department of Artificial Intelligence & Robotics Engineering, Al-Nahrain University, P.O. Box 64040, Al Jadriyah, Baghdad 10072, Iraq.
  • HEXACORP-AHI Carrier FZC (Automated Logic Corporation-A Carrier Company), Karrada-Al-Hurriya sq. 925/25/62-1, Baghdad 10069, Iraq.

ORCID-Profile: Abdulmohaymin Bassim Qassim, Shaimaa Mudhafar Hashim, Wajdi Sadik Aboud

Zitieren

APA

Qassim, A. B., Hashim, S. M., & Aboud, W. S. (2025). Design and Implementation of a Cascade Control System for a Variable Air Volume in Operating Rooms Based on Pressure and Temperature Feedback. Sensors. https://doi.org/10.3390/s25185656

Vancouver

Qassim AB, Hashim SM, Aboud WS. Design and Implementation of a Cascade Control System for a Variable Air Volume in Operating Rooms Based on Pressure and Temperature Feedback. Sensors. 2025. doi:10.3390/s25185656

BibTeX
@article{Qassim2025,
  author = {Qassim, Abdulmohaymin Bassim and Hashim, Shaimaa Mudhafar and Aboud, Wajdi Sadik},
  title = {Design and Implementation of a Cascade Control System for a Variable Air Volume in Operating Rooms Based on Pressure and Temperature Feedback},
  journal = {Sensors},
  year = {2025},
  doi = {10.3390/s25185656}
}
Kostenlos starten →