Locating Partial Discharges in Power Transformers with Convolutional Iterative Filtering
Sensors · 05.02.2023 · 23 (4) · 1789
DOI: 10.3390/s23041789 ↗Kurz gefasst
Fachartikel in der Zeitschrift Sensors, online erschienen am 05.02.2023. Verfasst von Jonathan Wang und 3 weiteren Autor:innen. Beteiligte Einrichtung: Lawrence Berkeley National Laboratory, Berkeley, CA 94720, USA. Die Arbeit wurde bisher 9-mal zitiert (Crossref) und nennt 36 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Office of Science of the U.S. Department of Energy, Scientific Discovery through Advanced Computing (SciDAC) program.
Abstract (Originalsprache)
The most common source of transformer failure is in the insulation, and the most prevalent warning signal for insulation weakness is partial discharge (PD). Locating the positions of these partial discharges would help repair the transformer to prevent failures. This work investigates algorithms that could be deployed to locate the position of a PD event using data from ultra-high frequency (UHF) sensors inside the transformer. These algorithms typically proceed in two steps: first determining the signal arrival time, and then locating the position based on time differences. This paper reviews available methods for each task and then propose new algorithms: a convolutional iterative filter with thresholding (CIFT) to determine the signal arrival time and a reference table of travel times to resolve the source location. The effectiveness of these algorithms are tested with a set of laboratory-triggered PD events and two sets of simulated PD events inside transformers in production use. Tests show the new approach provides more accurate locations than the best-known data analysis algorithms, and the difference is particularly large, 3.7X, when the signal sources are far from sensors.
Schlagwörter
Stichwörter der Autor:innen
Autor:innen und Institutionen
- Lawrence Berkeley National Laboratory, Berkeley, CA 94720, USA.
- Vitzrotech Co., Ltd., Seoul 425833, Republic of Korea.
ORCID-Profile: Kesheng Wu, Alex Sim
Förderung
- Office of Science of the U.S. Department of Energy
- Scientific Discovery through Advanced Computing (SciDAC) program
Zitieren
APA
Wang, J., Wu, K., Sim, A., & Hwangbo, S. (2023). Locating Partial Discharges in Power Transformers with Convolutional Iterative Filtering. Sensors, 23(4), 1789. https://doi.org/10.3390/s23041789
Vancouver
Wang J, Wu K, Sim A, Hwangbo S. Locating Partial Discharges in Power Transformers with Convolutional Iterative Filtering. Sensors. 2023;23(4):1789. doi:10.3390/s23041789
BibTeX
@article{Wang2023,
author = {Wang, Jonathan and Wu, Kesheng and Sim, Alex and Hwangbo, Seongwook},
title = {Locating Partial Discharges in Power Transformers with Convolutional Iterative Filtering},
journal = {Sensors},
year = {2023},
volume = {23},
number = {4},
pages = {1789},
doi = {10.3390/s23041789}
}
EUVIMED