EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Online Monitoring of Partial Discharges in Large Power Transformers Using Ultra-High Frequency and Acoustic Emission Methods: Case Studies

Wojciech Sikorski, Jaroslaw Gielniak

Energies · 29.03.2025 · 18 (7) · 1718

DOI: 10.3390/en18071718 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Energies, online erschienen am 29.03.2025. Verfasst von Wojciech Sikorski und 1 weiteren Autor:innen. Die Arbeit wurde bisher 14-mal zitiert (Crossref) und nennt 45 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Partial discharges (PDs) are one of the leading causes of catastrophic power transformer failures. To prevent such failures, online PD monitoring systems are increasingly being implemented. In this paper, to the best of the authors’ knowledge, a case study analysis of short-term PD monitoring is presented for the first time using a combination of acoustic emission and ultra-high-frequency methods. Studies have shown that this approach, supported by selected statistical methods for analyzing the convergence (such as the confusion matrix and agreement metrics) of acoustic and electromagnetic pulse detection, improves the reliability of PD detection. Furthermore, it was shown that short-term PD monitoring enables the identification of time windows during which discharges occur periodically and the determination of the transformer phase containing the PD source. This, in turn, facilitates the application of the time difference of arrival (TDoA) technique for the precise localization of transformer insulation defects.

Zitieren

APA

Sikorski, W., & Gielniak, J. (2025). Online Monitoring of Partial Discharges in Large Power Transformers Using Ultra-High Frequency and Acoustic Emission Methods: Case Studies. Energies, 18(7), 1718. https://doi.org/10.3390/en18071718

Vancouver

Sikorski W, Gielniak J. Online Monitoring of Partial Discharges in Large Power Transformers Using Ultra-High Frequency and Acoustic Emission Methods: Case Studies. Energies. 2025;18(7):1718. doi:10.3390/en18071718

BibTeX
@article{Sikorski2025,
  author = {Sikorski, Wojciech and Gielniak, Jaroslaw},
  title = {Online Monitoring of Partial Discharges in Large Power Transformers Using Ultra-High Frequency and Acoustic Emission Methods: Case Studies},
  journal = {Energies},
  year = {2025},
  volume = {18},
  number = {7},
  pages = {1718},
  doi = {10.3390/en18071718}
}