A Multiple-Fault Diagnosis Method for Non-Uniform Grounding Grids Based on Dynamic Topology Tearing
Infrastructures · 09.11.2026 · 11 (11) · 415
DOI: 10.3390/infrastructures11110415 ↗Kurz gefasst
Fachartikel in der Zeitschrift Infrastructures, online erschienen am 09.11.2026. Verfasst von Rui Zhou und 3 weiteren Autor:innen. Die Arbeit nennt 37 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: National Natural Science Foundation of China.
Abstract (Originalsprache)
Corrosion and conductor breaks in grounding grids can compromise the safe dissipation of substation fault currents. To diagnose these faults using only a limited number of accessible nodes, this study groups frequencies and selects reference-port impedances based on the distribution of injected currents throughout the grounding grid at different frequencies. The topology-tearing method retains all nodal voltages and employs equivalent sources to approximate the effects of currents in fixed branches. For a grounding grid comprising 49 branches, this method reduces the number of unknowns from 79 at low frequencies to 47 at high frequencies. The proposed hybrid algorithm (ERS-DBO-SQP) augments dung beetle optimization with reflection and scattering moves during stagnation and uses sequential quadratic programming for local refinement. In the selected timed run on this grid, ERS-DBO-SQP achieved a geometric mean of sensitivity and specificity of 0.8563 in 91.25 s of solver time. Three alternative solvers achieved 0.3801–0.4282 in 120.74–129.47 s. Numerical simulations, CDEGS simulations, and field tests demonstrate that the proposed method can effectively identify corrosion and conductor-break faults with high diagnostic accuracy.
Förderung
- National Natural Science Foundation of China
Zitieren
APA
Zhou, R., Cao, X., Shi, X., & Li, R. (2026). A Multiple-Fault Diagnosis Method for Non-Uniform Grounding Grids Based on Dynamic Topology Tearing. Infrastructures, 11(11), 415. https://doi.org/10.3390/infrastructures11110415
Vancouver
Zhou R, Cao X, Shi X, Li R. A Multiple-Fault Diagnosis Method for Non-Uniform Grounding Grids Based on Dynamic Topology Tearing. Infrastructures. 2026;11(11):415. doi:10.3390/infrastructures11110415
BibTeX
@article{Zhou2026,
author = {Zhou, Rui and Cao, Xiaobin and Shi, Xinyu and Li, Ruifang},
title = {A Multiple-Fault Diagnosis Method for Non-Uniform Grounding Grids Based on Dynamic Topology Tearing},
journal = {Infrastructures},
year = {2026},
volume = {11},
number = {11},
pages = {415},
doi = {10.3390/infrastructures11110415}
}
EUVIMED