Drone-assisted time-varying magnetic field analysis for fault diagnosis in grounding grids
PLOS One · 17.06.2025 · 20 (6) · e0325845
DOI: 10.1371/journal.pone.0325845 ↗Kurz gefasst
Fachartikel in der Zeitschrift PLOS One, online erschienen am 17.06.2025. Verfasst von Aamir Qamar und 1 weiteren Autor:innen. Beteiligte Einrichtung: Department of Electrical Engineering, COMSATS University Islamabd, Wah Campus, Wah, Punjab, Pakistan. Hauptthemen laut MEDLINE: Magnetic Fields, Electromagnetic Fields. Die Arbeit wurde bisher 5-mal zitiert (Crossref) und nennt 22 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Higher Education Commission (HEC) of Pakistan under the National Research Program for Universities.
Abstract (Originalsprache)
Grounding grids are essential for ensuring the safety of power substations, but their performance can degrade due to corrosion, fractures, or other faults. Traditional fault diagnosis methods are time-consuming, labor-intensive, and require physical access to substations, posing safety risks. This paper introduces a drone-based approach for magnetic field sensing to diagnose grounding grid faults, significantly reducing operational risks and improving efficiency. However, the movement of the drone introduces time-varying electromagnetic interference (EMI) from substation equipment and the drone itself, complicating the isolation of grounding grid signals. To address this problem, we propose a time-varying un-mixing technique combined with the Fast Independent Component Analysis (FastICA) algorithm to effectively suppress the EMI and extract the grounding grid signals. Simulation results demonstrate the efficacy of the proposed technique in separating grounding grid signals under time-varying conditions, outperforming the FastICA algorithm by 96.36% and the Independent Vector Analysis (IVA) by 41.17% at a block length of 4000 and Γ Δ k = 0.05 . These results highlight the robustness and applicability of the proposed approach for real-world grounding grid fault diagnosis, ensuring accuracy and safety in EMI-rich environments. However, the performance of the proposed technique degrades at higher values of Γ Δ k , which represents the speed of the flying drone.
Schlagwörter
MeSH-Schlagwörter (MEDLINE)
Autor:innen und Institutionen
- Department of Electrical Engineering, COMSATS University Islamabd, Wah Campus, Wah, Punjab, Pakistan.
ORCID-Profile: Aamir Qamar
Förderung
- Higher Education Commission (HEC) of Pakistan under the National Research Program for Universities
Zitieren
APA
Qamar, A., & Uddin, Z. (2025). Drone-assisted time-varying magnetic field analysis for fault diagnosis in grounding grids. PLOS One, 20(6), e0325845. https://doi.org/10.1371/journal.pone.0325845
Vancouver
Qamar A, Uddin Z. Drone-assisted time-varying magnetic field analysis for fault diagnosis in grounding grids. PLOS One. 2025;20(6):e0325845. doi:10.1371/journal.pone.0325845
BibTeX
@article{Qamar2025,
author = {Qamar, Aamir and Uddin, Zahoor},
title = {Drone-assisted time-varying magnetic field analysis for fault diagnosis in grounding grids},
journal = {PLOS One},
year = {2025},
volume = {20},
number = {6},
pages = {e0325845},
doi = {10.1371/journal.pone.0325845}
}
EUVIMED