Abstract (Originalsprache)

The long-term operational reliability of a valve-side bushing in High-Voltage Direct Current (HVDC) converter transformers depends heavily on the integrity of the spring contact. The existing literature has primarily focused on static defects under steady-state conditions. This study analyzes time-dependent temperature and electric field characteristics under both normal and spring contact defect conditions using a time-varying model accounting for harmonic-induced heating and temperature-dependent conductivity. Harmonic components were derived from operational waveforms of the Bukdangjin LCC-HVDC converter transformer valve-side bushing. Over an 8640 h simulation reaching a maximum contact hot-spot temperature of 107.789 °C, results revealed that under normal conditions, the radial field temporarily flattened at 937 h, with the gap between the first and final layers narrowing by 86.7% (from 2.593 to 0.345 kV/mm) before recovering at a steady state. Conversely, contact defects caused an electric field inversion: the final-layer field surged by 122.3% (from 1.39 to 3.09 kV/mm) at 937 h, exceeding the first layer (1.05 kV/mm) by 2.04 kV/mm, and remained inverted at 8640 h (2.97 vs. 2.14 kV/mm). Consequently, these findings demonstrate that bushing insulation experiences the most severe electro-thermal stress during the transient state, where contact-induced temperature gradients govern dielectric stress intensification at the outermost layers.

Förderung

  • Korea Electric Power Corporation

Zitieren

APA

Kim, G. H., Kwahk, Y. J., Lee, J. G., & Lee, B. W. (2026). Electric Field Distortion Under Transient Electro-Thermal Stresses in LCC-HVDC Valve Side Bushings with Spring Contact Defects. Energies, 19(22), 5505. https://doi.org/10.3390/en19225505

Vancouver

Kim GH, Kwahk YJ, Lee JG, Lee BW. Electric Field Distortion Under Transient Electro-Thermal Stresses in LCC-HVDC Valve Side Bushings with Spring Contact Defects. Energies. 2026;19(22):5505. doi:10.3390/en19225505

BibTeX
@article{Kim2026,
  author = {Kim, Gwan Hyeok and Kwahk, Yu Jin and Lee, Jong Geon and Lee, Bang Wook},
  title = {Electric Field Distortion Under Transient Electro-Thermal Stresses in LCC-HVDC Valve Side Bushings with Spring Contact Defects},
  journal = {Energies},
  year = {2026},
  volume = {19},
  number = {22},
  pages = {5505},
  doi = {10.3390/en19225505}
}
Kostenlos starten →