A Rectifier-Side Resistance Measurement-Based Method for Self-Initiated Fault Recovery in LCC-HVDC Systems
IEEE Transactions on Instrumentation and Measurement · 2026 · 75 · 9006613-9006613
DOI: 10.1109/tim.2026.3711323 ↗Kurz gefasst
Fachartikel in der Zeitschrift IEEE Transactions on Instrumentation and Measurement, 2026. Verfasst von Yayu Yang und 4 weiteren Autor:innen. Die Arbeit nennt 32 Literaturangaben. Gefördert von: National Natural Science Foundation of China.
Abstract (Originalsprache)
Accurately measuring the state of a DC line to distinguish between transient faults (TFs) and permanent faults (PFs) is a critical measurement challenge in line-commutated-converter high voltage direct current (LCC-HVDC) systems. In practical LCC-HVDC projects, the system typically treats faults as TFs and executes a restart operation, which may pose potential risks to the system. Existing measurement methods often suffer from low sensitivity to high-resistance faults. To solve this measurement problem, this article proposes a novel fault type identification method based on rectifier-side measured resistance (RSMR). The measurement principle relies on the clear distinction in the measured RSMR value: during PFs, the RSMR is low. In contrast, for TFs, the measured resistance is exceptionally high. By measuring the voltage and current at the rectifier station’s smoothing reactor valve side after the signal injection, the RSMR measurand is calculated to identify the fault type. Simulation results demonstrate that the proposed measurement method is simple, reliable, and exhibits high sensitivity and robustness over a wide range of fault resistances.
Förderung
- National Natural Science Foundation of China
Zitieren
APA
Yang, Y., Pei, Z., Wang, H., Gao, N., & Wang, K. (2026). A Rectifier-Side Resistance Measurement-Based Method for Self-Initiated Fault Recovery in LCC-HVDC Systems. IEEE Transactions on Instrumentation and Measurement, 75, 9006613-9006613. https://doi.org/10.1109/tim.2026.3711323
Vancouver
Yang Y, Pei Z, Wang H, Gao N, Wang K. A Rectifier-Side Resistance Measurement-Based Method for Self-Initiated Fault Recovery in LCC-HVDC Systems. IEEE Transactions on Instrumentation and Measurement. 2026;75:9006613-9006613. doi:10.1109/tim.2026.3711323
BibTeX
@article{Yang2026,
author = {Yang, Yayu and Pei, Zhijie and Wang, Haozong and Gao, Ning and Wang, Kangan},
title = {A Rectifier-Side Resistance Measurement-Based Method for Self-Initiated Fault Recovery in LCC-HVDC Systems},
journal = {IEEE Transactions on Instrumentation and Measurement},
year = {2026},
volume = {75},
pages = {9006613--9006613},
doi = {10.1109/tim.2026.3711323}
}