EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Multi-Parameter Sensitivity Analysis and Engineering Configuration Optimization Strategies for Sheath Protectors in 220 kV Cable Systems Based on Overvoltage Characteristic Analysis

Xiaoyan Ji, Yong Liu, Qiran Li

Energies · 21.06.2026 · 19 (12) · 2929

DOI: 10.3390/en19122929 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Energies, online erschienen am 21.06.2026. Verfasst von Xiaoyan Ji und 2 weiteren Autor:innen. Die Arbeit nennt 18 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

This paper focuses on 220 kV cable sheath overvoltage caused by three typical operating conditions: harmonics, short-circuits, and lightning strikes. A sheath voltage simulation model on the 220 kV side is developed in PSCAD. Through multi-parameter scanning and sensitivity analysis, the overvoltage characteristics and key influencing factors are systematically studied, and engineering optimization strategies for sheath protector configuration are proposed for different types of overvoltage. Under harmonic conditions, a suppression circuit composed of discharge capacitance and discharge resistors is proposed to attenuate high-frequency disturbances. Under high-amplitude overvoltage conditions such as short-circuits and lightning strikes, the sheath protector configuration is optimized by adjusting cable length and grounding configuration. Under large current conditions, a parallel configuration scheme for sheath protectors is proposed from the perspective of energy absorption. Multi-condition simulations are conducted, and a simulation-based case study is carried out based on the actual layout and parameters of a traction substation cable line. The results show that the proposed strategies can effectively reduce the peak value of sheath overvoltage, providing simulation-based quantitative engineering guidance for the configuration of 220 kV cable sheath protectors based on sensitivity analysis results.

Zitieren

APA

Ji, X., Liu, Y., & Li, Q. (2026). Multi-Parameter Sensitivity Analysis and Engineering Configuration Optimization Strategies for Sheath Protectors in 220 kV Cable Systems Based on Overvoltage Characteristic Analysis. Energies, 19(12), 2929. https://doi.org/10.3390/en19122929

Vancouver

Ji X, Liu Y, Li Q. Multi-Parameter Sensitivity Analysis and Engineering Configuration Optimization Strategies for Sheath Protectors in 220 kV Cable Systems Based on Overvoltage Characteristic Analysis. Energies. 2026;19(12):2929. doi:10.3390/en19122929

BibTeX
@article{Ji2026,
  author = {Ji, Xiaoyan and Liu, Yong and Li, Qiran},
  title = {Multi-Parameter Sensitivity Analysis and Engineering Configuration Optimization Strategies for Sheath Protectors in 220 kV Cable Systems Based on Overvoltage Characteristic Analysis},
  journal = {Energies},
  year = {2026},
  volume = {19},
  number = {12},
  pages = {2929},
  doi = {10.3390/en19122929}
}
Kostenlos starten →