Ignition of Vegetation Induced by Discharge from Abraded Medium-Voltage Insulated Overhead Lines
Energies · 2026-04-20 · 19 (8) · 1990
DOI: 10.3390/en19081990 ↗At a glance
Journal article in Energies, published online on 2026-04-20. Written by Tian Tan and 6 co-authors. Cited 1 times so far (Crossref); 27 references. The full text is freely available (open access, CC BY 4.0). Funded by: National Natural Science Foundation of China, Natural Science Foundation of Hunan Province, China, Natural Science Fund of Changsha.
Abstract (original language)
Tree contact discharge is a key contributing factor to wildfires caused by medium-voltage insulated conductors. Prolonged abrasion of the insulation layer by branches gradually creates weak points in the insulation. When subjected to lightning strikes, these areas are prone to forming lightning-induced pinholes, which can subsequently trigger partial discharge and even ignition. This study systematically investigates the discharge-induced ignition mechanism for 10 kV overhead insulated conductors in tree contact scenarios by establishing an experimental platform integrated with high-speed imaging, ultraviolet detection, and simulation methods. Three types of typical defects were set up in the experiments: complete insulation abrasion, lightning puncture holes accompanied by localized abrasion, and lightning puncture holes without abrasion. The development process and characteristics of different discharge forms were observed and analyzed. The results indicate that the tree contact discharge ignition mechanism can be categorized into two types: thermal accumulation and direct arcing. The former occurs when insulation abrasion or composite defects exist, where sustained partial discharge or a high-resistance current leads to gradual heat accumulation, resulting in an ignition delay lasting tens of seconds. The latter occurs when only small defects such as lightning puncture holes exist in the insulation layer. A concentrated arc forms due to gap breakdown under high voltage, leading to a millisecond-level ignition process. The study found that different discharge forms produce significantly distinct ablation and carbonization patterns on both the insulation layer and the branch surface, reflecting differences in energy transfer pathways. Simulation analysis further indicated that the thickness of the insulation layer affects the electric field distribution in the tree contact gap, with the initial discharge field strength decreasing as the thickness increases. This study provides experimental evidence and classification guidance for tree contact fault monitoring, insulation condition assessment, and wildfire prevention and control in medium-voltage distribution networks.
Funding
- National Natural Science Foundation of China
- Natural Science Foundation of Hunan Province, China
- Natural Science Fund of Changsha
- Postgraduate Scientific Research Innovation Project of Changsha University of Science and Technology University
Cite
APA
Tan, T., Peng, H., Yang, X., Liu, J., Li, M., Fu, S., & Huang, Y. (2026). Ignition of Vegetation Induced by Discharge from Abraded Medium-Voltage Insulated Overhead Lines. Energies, 19(8), 1990. https://doi.org/10.3390/en19081990
Vancouver
Tan T, Peng H, Yang X, Liu J, Li M, Fu S, et al. Ignition of Vegetation Induced by Discharge from Abraded Medium-Voltage Insulated Overhead Lines. Energies. 2026;19(8):1990. doi:10.3390/en19081990
BibTeX
@article{Tan2026,
author = {Tan, Tian and Peng, Huajian and Yang, Xin and Liu, Jiaxi and Li, Mingzhe and Fu, Shuaiwei and Huang, Yafei},
title = {Ignition of Vegetation Induced by Discharge from Abraded Medium-Voltage Insulated Overhead Lines},
journal = {Energies},
year = {2026},
volume = {19},
number = {8},
pages = {1990},
doi = {10.3390/en19081990}
}
EUVIMED