Faulty Line Selection Method Based on Differentiation of Zero-Sequence Current Characteristics for Flexible Grounding Systems

Yafeng Huang, Junhang Ye, Jiaqing Sun

Electronics · 2026-04-21 · 15 (8) · 1754

DOI: 10.3390/electronics15081754 ↗

At a glance

Journal article in Electronics, published online on 2026-04-21. Written by Yafeng Huang and 2 co-authors. Cited 1 times so far (Crossref); 38 references. The full text is freely available (open access, CC BY 4.0).

AbstractBibliografiske oplysningerCiteRelated studies

Abstract (original language)

To effectively address the challenge of faulty line selection during high-impedance grounding faults in distribution networks with a flexible grounding system, a novel fault line selection method that integrates both the amplitude and phase characteristics of zero-sequence currents is proposed. The characteristics of zero-sequence currents under single-phase grounding faults in a flexible grounding system are thoroughly investigated, with a particular focus on analyzing the phase relationship and amplitude differences between the zero-sequence currents of each feeder and that of the neutral point. Upon the switching of the parallel low-resistance device, the zero-sequence current of the faulty line is approximately equal in amplitude but opposite in phase to that of the neutral point. In contrast, the zero-sequence current amplitude of a healthy line is significantly smaller than that of the neutral point, and its phase is nearly orthogonal to the neutral point zero-sequence current. To capture these characteristic differences, the projection of each line’s zero-sequence current onto the neutral point zero-sequence current is employed. A projection coefficient criterion is subsequently constructed to enhance the reliability of line selection. Furthermore, by utilizing the neutral point zero-sequence current, the method can effectively extract the weak zero-sequence current of healthy lines, thereby mitigating the risk of misjudgment by the fault line selection device caused by the inability of zero-sequence current transformers (CT) to accurately acquire such faint signals. Simulation results obtained via PSCAD validate that the proposed method remains effective for single-phase grounding faults with transition resistances up to 3000 Ω, even under extreme operating conditions such as reverse polarity of zero-sequence CT or the presence of strong noise interference.

Cite

APA

Huang, Y., Ye, J., & Sun, J. (2026). Faulty Line Selection Method Based on Differentiation of Zero-Sequence Current Characteristics for Flexible Grounding Systems. Electronics, 15(8), 1754. https://doi.org/10.3390/electronics15081754

Vancouver

Huang Y, Ye J, Sun J. Faulty Line Selection Method Based on Differentiation of Zero-Sequence Current Characteristics for Flexible Grounding Systems. Electronics. 2026;15(8):1754. doi:10.3390/electronics15081754

BibTeX
@article{Huang2026,
  author = {Huang, Yafeng and Ye, Junhang and Sun, Jiaqing},
  title = {Faulty Line Selection Method Based on Differentiation of Zero-Sequence Current Characteristics for Flexible Grounding Systems},
  journal = {Electronics},
  year = {2026},
  volume = {15},
  number = {8},
  pages = {1754},
  doi = {10.3390/electronics15081754}
}
Start for free →