Investigation of Optimal Installation Positions for Two Coherent Motors to Minimize Structure-Borne Sound Transmission to a Floor in Buildings
Buildings · 17.03.2026 · 16 (6) · 1176
DOI: 10.3390/buildings16061176 ↗Kurz gefasst
Fachartikel in der Zeitschrift Buildings, online erschienen am 17.03.2026. Verfasst von Zhen Wang und 1 weiteren Autor:innen. Die Arbeit nennt 35 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).
Abstract (Originalsprache)
This paper investigates the optimal installation positions of two coherent motors by analyzing the structure-borne sound power transmission to a simply supported rectangular concrete floor. The free velocity and source mobility of the motors were measured experimentally, while the receiver mobility of the floor was obtained via the modal summation method. Based on these parameters, the study examined how installation positions and inter-point interactions influence the transmitted sound power. The results showed that the difference in structure-borne sound power level between the optimal and worst-case installations was 20.44 dB in the 1/3-octave band centered at 50 Hz. Crucially, the optimal positions remained unchanged even when inter-point interactions were neglected in the power calculations, providing actionable guidance for practical vibration isolation design in building applications.
Zitieren
APA
Wang, Z., & Mak, C. M. (2026). Investigation of Optimal Installation Positions for Two Coherent Motors to Minimize Structure-Borne Sound Transmission to a Floor in Buildings. Buildings, 16(6), 1176. https://doi.org/10.3390/buildings16061176
Vancouver
Wang Z, Mak CM. Investigation of Optimal Installation Positions for Two Coherent Motors to Minimize Structure-Borne Sound Transmission to a Floor in Buildings. Buildings. 2026;16(6):1176. doi:10.3390/buildings16061176
BibTeX
@article{Wang2026,
author = {Wang, Zhen and Mak, Cheuk Ming},
title = {Investigation of Optimal Installation Positions for Two Coherent Motors to Minimize Structure-Borne Sound Transmission to a Floor in Buildings},
journal = {Buildings},
year = {2026},
volume = {16},
number = {6},
pages = {1176},
doi = {10.3390/buildings16061176}
}