The Effect of Conductor Geometry on Electric Field Distribution in Air-Insulated Medium Voltage Busbar Systems
Applied Sciences · 07.11.2026 · 16 (21) · 11024
DOI: 10.3390/app162111024 ↗Kurz gefasst
Fachartikel in der Zeitschrift Applied Sciences, online erschienen am 07.11.2026. Verfasst von Ahmet Can Yalcin und 3 weiteren Autor:innen. Die Arbeit nennt 35 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).
Abstract (Originalsprache)
In the design processes of medium-voltage (MV) systems, ensuring insulation safety is considered a critical parameter in terms of both system sustainability and the service life of the components used. In this study, the direct effects of the cross-sectional geometry of conductors used in air-insulated switchgear (AIS) systems on electric field distribution and dielectric strength characteristics were quantitatively investigated through numerical analysis methods. Within the scope of the research, conductor models with different geometric structures were created based on a rated line-to-line voltage level of 17.5 kV, and these models were analyzed using the finite element method with COMSOL Multiphysics® (AC/DC Module 6.2 version) software under the rated peak inter-phase potential difference (24.75 kV). Simulation studies demonstrate that curved transitions at the rounded edges on conductor surfaces cause electric field lines to concentrate at these boundaries, leading to local electric field intensification. In calculations performed on a standard rectangular cross-section conductor with dimensions CU-6 × 180 mm, the maximum electric field strength reached 10.90 kV/cm at the rounded edges. For wider rectangular profiles such as CU-12 × 220 mm and CU-12 × 360 mm, maximum field strengths remained at 7.77 kV/cm and 7.42 kV/cm, respectively. In contrast, adopting equal-area cylindrical configurations for these profiles reduced the peak electric field to 4.54 kV/cm (for the 12 × 220 mm equivalent) and 4.22 kV/cm (for the 12 × 360 mm equivalent) owing to the uniform charge distribution across the continuous cylindrical boundary. Beyond the qualitative understanding of electrostatic curvature, this study quantitatively benchmarks the dielectric safety margins and field utilization factors for standardized industrial MV busbar profiles at 17.5 kV, providing practical geometric criteria for partial discharge mitigation in compact switchgear designs. The findings indicate that profile geometry serves as an effective design measure in mitigating electrical stress and reducing partial discharge risk in medium-voltage equipment.
Zitieren
APA
Yalcin, A. C., Akdemir, H., Uydur, C. C., & Dursun, B. (2026). The Effect of Conductor Geometry on Electric Field Distribution in Air-Insulated Medium Voltage Busbar Systems. Applied Sciences, 16(21), 11024. https://doi.org/10.3390/app162111024
Vancouver
Yalcin AC, Akdemir H, Uydur CC, Dursun B. The Effect of Conductor Geometry on Electric Field Distribution in Air-Insulated Medium Voltage Busbar Systems. Applied Sciences. 2026;16(21):11024. doi:10.3390/app162111024
BibTeX
@article{Yalcin2026,
author = {Yalcin, Ahmet Can and Akdemir, Huseyin and Uydur, Cihat Cagdas and Dursun, Bekir},
title = {The Effect of Conductor Geometry on Electric Field Distribution in Air-Insulated Medium Voltage Busbar Systems},
journal = {Applied Sciences},
year = {2026},
volume = {16},
number = {21},
pages = {11024},
doi = {10.3390/app162111024}
}
EUVIMED