Ventilation Effectiveness Measurements in Clean and Dry Rooms Based on Tracer Gas Techniques—A Preliminary Measurement Development
Applied Sciences · 05.07.2026 · 16 (13) · 6732
DOI: 10.3390/app16136732 ↗Kurz gefasst
Fachartikel in der Zeitschrift Applied Sciences, online erschienen am 05.07.2026. Verfasst von Simon Leisner und 4 weiteren Autor:innen. Die Arbeit nennt 24 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).
Abstract (Originalsprache)
Battery cell manufacturing is highly energy intensive, with clean and dry rooms being among the largest consumers of electricity and thermal energy. Due to the moisture sensitivity of most advanced cathode materials (e.g., NMC 811) and sulfide-based solid-state materials, production environments must operate at extremely low humidity, requiring energy-intensive HVAC systems to remove moisture introduced mainly by workers and infiltration. To reduce energy consumption, a detailed understanding of the airflow patterns in the room is essential. Because of complex flow patterns (exhaust air demands, energy dissipation), tracer gas techniques using CO2 as a marker provide an operation-integrated method for determining local air age. The studies presented in this paper apply tracer gas techniques for the first time to a room in which air is almost completely recirculated at high air change rates of approximately 27 h−1, with the supply air being conditioned by removing all process-relevant contaminants such as moisture and particles. Measurements in a separate flow box show successful air age calculations that agree with simplified CFD simulations. For the clean and dry room, the empirical variable relative exposure (REX) was introduced. The measurements indicate an inhomogeneous air distribution inside the room, accompanied with short-circuit flows, partial displacement flow, and mixing, and therefore have the potential to provide a cost-effective first-hand insight into the prevailing airflow patterns. Nevertheless, the presented measurement technique must be further optimized and validated for rooms with air recirculation and high air change rates.
Zitieren
APA
Leisner, S., Zhou, X., Li, Z., Kissling, M., & Auerswald, S. (2026). Ventilation Effectiveness Measurements in Clean and Dry Rooms Based on Tracer Gas Techniques—A Preliminary Measurement Development. Applied Sciences, 16(13), 6732. https://doi.org/10.3390/app16136732
Vancouver
Leisner S, Zhou X, Li Z, Kissling M, Auerswald S. Ventilation Effectiveness Measurements in Clean and Dry Rooms Based on Tracer Gas Techniques—A Preliminary Measurement Development. Applied Sciences. 2026;16(13):6732. doi:10.3390/app16136732
BibTeX
@article{Leisner2026,
author = {Leisner, Simon and Zhou, Xinyue and Li, Ziyue and Kissling, Marc and Auerswald, Sven},
title = {Ventilation Effectiveness Measurements in Clean and Dry Rooms Based on Tracer Gas Techniques—A Preliminary Measurement Development},
journal = {Applied Sciences},
year = {2026},
volume = {16},
number = {13},
pages = {6732},
doi = {10.3390/app16136732}
}