What is the effect of reducing the air change rate on the ventilation effectiveness in ultra-clean operating rooms?
Journal of Hospital Infection · 2024-05 · 147 · 115-122
DOI: 10.1016/j.jhin.2024.02.007 ↗Kurz gefasst
Fachartikel in der Zeitschrift Journal of Hospital Infection, 2024-05. Verfasst von J L A Lans und 5 weiteren Autor:innen. Beteiligte Einrichtung: Faculty Architecture and the Built Environment, Delft University of Technology, Delft, The Netherlands. Electronic address: j.l.a.lans@tudelft.nl. Hauptthemen laut MEDLINE: Operating Rooms, Ventilation. Die Arbeit wurde bisher 12-mal zitiert (Crossref) und nennt 32 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).
Abstract (Originalsprache)
BACKGROUND: The operating room (OR) department is one of the most energy-intensive departments of a hospital. The majority of ORs in the Netherlands have an air-handling installation with an ultra-clean ventilation system. However, not all surgeries require an ultra-clean OR. AIM: To determine the effect of reducing the air change rate on the ventilation effectiveness in ultra-clean ORs. METHODS: Lower air volume ventilation effectiveness (VELv) of conventional ventilation (CV), controlled dilution ventilation (cDV), temperature-controlled airflow (TcAF) and unidirectional airflow (UDAF) systems were evaluated within a 4 × 4 m measuring grid of 1 × 1 m. The VELv was defined as the recovery degree (RD), cleanliness recovery rate (CRR) and air change effectiveness (ACE). FINDINGS: The CV, cDVLv and TcAFLv ventilation systems showed a comparable mixing character in all areas (A, B and AB) when reducing the air change rate to 20/h. Ventilation effectiveness decreased when the air change rate was reduced, with the exception of the ACE. At all points for the UDAF-2Lv and at the centre point (C3) of the TcAFLv, higher RD10Lv and CRRLv were measured when compared with the other examined ventilation systems. CONCLUSIONS: The ventilation effectiveness decreased when an ultra-clean OR with an ultra-clean ventilation air-supply system was switched to an air change rate of 20/h. Reducing the air change rate in the OR from an ultra-clean OR to a generic OR will reduce the recovery degree (RD10) by a factor of 10-100 and the local air change rate (CRR) by between 42% and 81%.
Schlagwörter
MeSH-Schlagwörter (MEDLINE)
Stichwörter der Autor:innen
Autor:innen und Institutionen
- Faculty Architecture and the Built Environment, Delft University of Technology, Delft, The Netherlands. Electronic address: j.l.a.lans@tudelft.nl.
- RHOC, Reinier Haga Orthopaedic Center, Zoetermeer, The Netherlands; Department of Orthopaedic Surgery, Reinier de Graaf Hospital, Delft, The Netherlands.
- Expert/Advisor Healthcare and Construction, IJsselstein, The Netherlands.
- Faculty of Mechanical Engineering (ME), Delft University of Technology, Delft, The Netherlands.
- Faculty of Mechanical Engineering (ME), Delft University of Technology, Delft, The Netherlands; Department of Trauma surgery, Reinier de Graaf Hospital, Delft, The Netherlands.
- Faculty Architecture and the Built Environment, Delft University of Technology, Delft, The Netherlands.
Zitieren
APA
Lans, J. L. A., Mathijssen, N. M. C., Bode, A., van den Dobbelsteen, J. J., van der Elst, M., & Luscuere, P. G. (2024). What is the effect of reducing the air change rate on the ventilation effectiveness in ultra-clean operating rooms?. Journal of Hospital Infection, 147, 115-122. https://doi.org/10.1016/j.jhin.2024.02.007
Vancouver
Lans JLA, Mathijssen NMC, Bode A, van den Dobbelsteen JJ, van der Elst M, Luscuere PG. What is the effect of reducing the air change rate on the ventilation effectiveness in ultra-clean operating rooms?. Journal of Hospital Infection. 2024;147:115-122. doi:10.1016/j.jhin.2024.02.007
BibTeX
@article{Lans2024,
author = {Lans, J L A and Mathijssen, N M C and Bode, A and van den Dobbelsteen, J J and van der Elst, M and Luscuere, P G},
title = {What is the effect of reducing the air change rate on the ventilation effectiveness in ultra-clean operating rooms?},
journal = {Journal of Hospital Infection},
year = {2024},
volume = {147},
pages = {115--122},
doi = {10.1016/j.jhin.2024.02.007}
}
EUVIMED