Hidden Harmonic Asymmetry in a Balanced Three-Phase Building: Evidence from Field Measurements

Franjo Pranjić, Peter Virtič

Applied Sciences · 06.06.2026 · 16 (12) · 5727

DOI: 10.3390/app16125727 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Applied Sciences, online erschienen am 06.06.2026. Verfasst von Franjo Pranjić und 1 weiteren Autor:innen. Die Arbeit wurde bisher 1-mal zitiert (Crossref) und nennt 24 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

The increasing penetration of power electronic devices and distributed generation is significantly altering power quality conditions in low-voltage systems. While power quality assessment is commonly based on RMS currents, voltage quality indicators, and overall distortion metrics, these parameters may not fully reveal phase-selective harmonic behaviour in modern converter-dominated installations. This paper presents a measurement-based power quality assessment of a secondary school building equipped with a grid-connected photovoltaic (PV) system. A one-week monitoring campaign was conducted at the point of common coupling (PCC), capturing voltage, current, harmonic distortion, and power flow characteristics under real operating conditions. The results reveal pronounced phase-selective current harmonic distortion, with substantially elevated total harmonic distortion (THD_I) and total demand distortion (TDD) in one phase despite relatively balanced RMS current levels and acceptable voltage quality. The harmonic spectrum is dominated by low-order odd harmonics, whereas voltage distortion remains comparatively low and well balanced across phases. The study demonstrates that significant harmonic asymmetry may remain hidden in apparently balanced three-phase systems when assessment relies primarily on conventional RMS-based indicators. The findings highlight the importance of detailed current harmonic analysis and show that acceptable voltage quality does not necessarily imply acceptable current quality. The presented results provide measurement-based evidence of hidden harmonic asymmetry in modern low-voltage buildings and contribute to a better understanding of power quality challenges associated with nonlinear loads and distributed energy resources.

Zitieren

APA

Pranjić, F., & Virtič, P. (2026). Hidden Harmonic Asymmetry in a Balanced Three-Phase Building: Evidence from Field Measurements. Applied Sciences, 16(12), 5727. https://doi.org/10.3390/app16125727

Vancouver

Pranjić F, Virtič P. Hidden Harmonic Asymmetry in a Balanced Three-Phase Building: Evidence from Field Measurements. Applied Sciences. 2026;16(12):5727. doi:10.3390/app16125727

BibTeX
@article{Pranji2026,
  author = {Pranjić, Franjo and Virtič, Peter},
  title = {Hidden Harmonic Asymmetry in a Balanced Three-Phase Building: Evidence from Field Measurements},
  journal = {Applied Sciences},
  year = {2026},
  volume = {16},
  number = {12},
  pages = {5727},
  doi = {10.3390/app16125727}
}
Kostenlos starten →