Single-Tuned Passive Filter for Harmonic and Transformer Derating Mitigation at Airlangga University Distribution System

Wahyu Setyawan, Aris Heri Andriawan, Reza Sarwo Widagdo

Jurnal JEETech · 09.11.2026 · 7 (2) · 266-281

DOI: 10.32492/jeetech.v7i2.7208 ↗

Kurz gefasst

Fachartikel in der Zeitschrift Jurnal JEETech, online erschienen am 09.11.2026. Verfasst von Wahyu Setyawan und 2 weiteren Autor:innen. Der Volltext ist frei zugänglich (Open Access, CC BY-NC 4.0).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Harmonic distortion caused by nonlinear loads can increase transformer losses and reduce its effective operating capability, even when the transformer operates under relatively low loading conditions. This study evaluates harmonic distortion and transformer derating in the electrical distribution system of the Nanizar Zaman Joenoes Building at Airlangga University and investigates the effectiveness of a single-tuned passive filter in mitigating these effects. Field measurements were conducted at the main distribution panel connected to the secondary side of a 1.6 MVA, 20 kV/400 V transformer operating at approximately 20–22% loading. The measured voltage harmonic distortion remained below the adopted limit, while the measured current distortion indicated significant lower-order harmonic components, with TDD values of 18.61%, 15.23%, and 14.40% for phases R, S, and T, respectively. K-Factor-based analysis indicated an initial transformer derating of 15.00%. A 5th-order single-tuned passive filter was subsequently designed at 250 Hz with a reactive power rating of 114.4 kVAr, a capacitance of 2276 µF, an inductance of 0.178 mH, and a resistance of 0.00559 Ω. ETAP simulation showed that the proposed filter reduced THDi from 10.37% to 5.01%, improved the power factor from 66.37% to 86.21%, and reduced transformer derating from 15.00% to 3.48%. The main contribution of this study is the integrated evaluation of harmonic mitigation and transformer operating-capability recovery in a lightly loaded building distribution transformer. The results demonstrate the potential of a properly tuned passive filter to reduce harmonic-related transformer derating, while field validation under varying load conditions remains necessary

Zitieren

APA

Setyawan, W., Andriawan, A. H., & Widagdo, R. S. (2026). Single-Tuned Passive Filter for Harmonic and Transformer Derating Mitigation at Airlangga University Distribution System. Jurnal JEETech, 7(2), 266-281. https://doi.org/10.32492/jeetech.v7i2.7208

Vancouver

Setyawan W, Andriawan AH, Widagdo RS. Single-Tuned Passive Filter for Harmonic and Transformer Derating Mitigation at Airlangga University Distribution System. Jurnal JEETech. 2026;7(2):266-281. doi:10.32492/jeetech.v7i2.7208

BibTeX
@article{Setyawan2026,
  author = {Setyawan, Wahyu and Andriawan, Aris Heri and Widagdo, Reza Sarwo},
  title = {Single-Tuned Passive Filter for Harmonic and Transformer Derating Mitigation at Airlangga University Distribution System},
  journal = {Jurnal JEETech},
  year = {2026},
  volume = {7},
  number = {2},
  pages = {266--281},
  doi = {10.32492/jeetech.v7i2.7208}
}
Kostenlos starten →