Air disinfection effect of different disinfection methods in high‐risk healthcare spaces

Jiamin Wang iD, Mengge Han, Yixin Cui, Wei Sun, Yan Shen, Jiabing Lin, Xiang Chen, Wenbo Wan, Bijie Hu, Xiaodong Gao

Photochemistry and Photobiology · 2026-11-09

DOI: 10.1111/php.70165 ↗

At a glance

Journal article in Photochemistry and Photobiology, published online on 2026-11-09. Written by Jiamin Wang and 9 co-authors. Institution: Department of Hospital Infection Management, Zhongshan Hospital, Fudan University, Shanghai, China. 24 references. Funded by: The Discipline construction project of the Institute of Hospital Infection and Control, Fudan University, Shanghai Project for Capacity Building of Infection Control in Healthcare Settings and Laboratory Biosafety, Key Disciplines of the Three-Year Action Plan for Strengthening the Public Health System in Shanghai (2023-2025).

TiivistelmäSubjectsBibliografiset tiedotCiteRelated studies

Abstract (original language)

To evaluate the field performance of human‐occupied air disinfection strategies in high‐risk healthcare areas, field tests were conducted in the high‐risk triage area, infectious disease ward, and dental clinics of a top‐tier academic medical center. Existing air disinfection or ventilation‐based control measures, including plasma air disinfection devices, ultraviolet (UV) air cleaners, and negative‐pressure ventilation systems, were evaluated alone or in combination with a 222‐nm UV upper‐room air disinfection system. No air disinfection intervention was used in the control group. Air sampling was performed hourly during daytime clinical hours using a six‐stage impactor microbial sampling method or a settle plate method. Compared with no‐disinfection controls or existing‐measure comparators, airborne bacterial concentrations were generally lower in the 222‐nm UV group or 222‐nm UV add‐on groups across multiple clinical settings. Percentage reductions relative to valid comparators ranged from 48.04% to 73.74% for 222‐nm UV alone and from 6.86% to 73.77% for 222‐nm UV used as an add‐on to existing measures. These findings suggest that 222‐nm UV upper‐room air disinfection may reduce airborne bacterial concentrations and improve air hygiene quality under routine clinical conditions. Because the study was not designed to determine mechanistic synergy, observed reductions in combined‐use groups are presented as add‐on field performance rather than evidence of synergistic interaction.

Subjects

Author keywords

222‐nm ultravioletair disinfectionhealthcare settingsoccupied healthcare spaceupper‐room air disinfection

Authors and institutions

  • Department of Hospital Infection Management, Zhongshan Hospital, Fudan University, Shanghai, China.
  • Institute of Hospital Infection and Control, Fudan University, Shanghai, China.
  • Shanghai Institute of Infectious Disease and Biosecurity, Fudan University, Shanghai, China.
  • Department of Infectious Diseases, Zhongshan Hospital, Fudan University, Shanghai, China.

ORCID profiles: Jiamin Wang

Funding

  • The Discipline construction project of the Institute of Hospital Infection and Control, Fudan University
  • Shanghai Project for Capacity Building of Infection Control in Healthcare Settings and Laboratory Biosafety
  • Key Disciplines of the Three-Year Action Plan for Strengthening the Public Health System in Shanghai (2023-2025)

Cite

APA

Wang, J., Han, M., Cui, Y., Sun, W., Shen, Y., Lin, J., Chen, X., Wan, W., Hu, B., & Gao, X. (2026). Air disinfection effect of different disinfection methods in high‐risk healthcare spaces. Photochemistry and Photobiology. https://doi.org/10.1111/php.70165

Vancouver

Wang J, Han M, Cui Y, Sun W, Shen Y, Lin J, et al. Air disinfection effect of different disinfection methods in high‐risk healthcare spaces. Photochemistry and Photobiology. 2026. doi:10.1111/php.70165

BibTeX
@article{Wang2026,
  author = {Wang, Jiamin and Han, Mengge and Cui, Yixin and Sun, Wei and Shen, Yan and Lin, Jiabing and Chen, Xiang and Wan, Wenbo and Hu, Bijie and Gao, Xiaodong},
  title = {Air disinfection effect of different disinfection methods in high‐risk healthcare spaces},
  journal = {Photochemistry and Photobiology},
  year = {2026},
  doi = {10.1111/php.70165}
}
Start for free →