Faulty Feeder Detection for Successive Single Phase-to-Ground Faults Based on Complete Waveform Recognition and Segmentation Evaluation
IEEE Transactions on Smart Grid · 2025-11 · 16 (6) · 4502-4516
DOI: 10.1109/tsg.2025.3593534 ↗Kurz gefasst
Fachartikel in der Zeitschrift IEEE Transactions on Smart Grid, 2025-11. Verfasst von Jiawei Yuan und 6 weiteren Autor:innen. Die Arbeit wurde bisher 6-mal zitiert (Crossref) und nennt 27 Literaturangaben. Gefördert von: National Natural Science Foundation of China, China Postdoctoral Science Foundation, Postdoctoral Fellowship Program (Grade C) of China Postdoctoral Science Foundation.
Abstract (Originalsprache)
When a single phase-to-ground (SPG) fault occurs in active distribution networks, over-voltage in healthy phases can potentially initiate a secondary SPG fault in other feeders. Existing detection techniques can only work under SPG faults while fail to identify the faulty feeders under this type of successive single phase-to-ground (SSPG) faults. To eliminate the blind zone of the existing methods, a novel hybrid data-physics driven detection method based on complete waveform recognition and segmentation evaluation is proposed in this paper. Firstly, the fault characteristics of zero-sequence currents (ZSC) under SSPG faults are analyzed. Secondly, a data-driven waveform recognition approach is introduced, utilizing the proposed deep feature fusion network to precisely extract complete fault characteristics from weak ZSCs. Thirdly, a comprehensive identification criterion is developed based on segmentation evaluation of the recognition results, with the physical mechanism of SSPG faults embedded into the process. In this framework, faulty feeders are identified through the effective integration of SSPG fault occurrence detection, fault component extraction, and feeder differentiation, thus significantly enhancing the detection reliability. Large amounts of simulation data and recorded data validate the satisfactory detection performance of the proposed method under various fault scenarios, illustrating its promising application prospects.
Förderung
- National Natural Science Foundation of China
- China Postdoctoral Science Foundation
- Postdoctoral Fellowship Program (Grade C) of China Postdoctoral Science Foundation
Zitieren
APA
Yuan, J., Dong, X., Liu, X., Ji, Y., Wang, Q., Chen, X., & Jiao, Z. (2025). Faulty Feeder Detection for Successive Single Phase-to-Ground Faults Based on Complete Waveform Recognition and Segmentation Evaluation. IEEE Transactions on Smart Grid, 16(6), 4502-4516. https://doi.org/10.1109/tsg.2025.3593534
Vancouver
Yuan J, Dong X, Liu X, Ji Y, Wang Q, Chen X, et al. Faulty Feeder Detection for Successive Single Phase-to-Ground Faults Based on Complete Waveform Recognition and Segmentation Evaluation. IEEE Transactions on Smart Grid. 2025;16(6):4502-4516. doi:10.1109/tsg.2025.3593534
BibTeX
@article{Yuan2025,
author = {Yuan, Jiawei and Dong, Xuan and Liu, Xintong and Ji, Yueming and Wang, Qiyang and Chen, Xi and Jiao, Zaibin},
title = {Faulty Feeder Detection for Successive Single Phase-to-Ground Faults Based on Complete Waveform Recognition and Segmentation Evaluation},
journal = {IEEE Transactions on Smart Grid},
year = {2025},
volume = {16},
number = {6},
pages = {4502--4516},
doi = {10.1109/tsg.2025.3593534}
}