Measurement System of the Mean and Sub-Cycle LV Grid Access Impedance From 20 kHz To 10 MHz
IEEE Transactions on Power Delivery · 2023-06 · 38 (3) · 2204-2212
DOI: 10.1109/tpwrd.2023.3238647 ↗Kurz gefasst
Fachartikel in der Zeitschrift IEEE Transactions on Power Delivery, 2023-06. Verfasst von Igor Fernández und 6 weiteren Autor:innen. Die Arbeit wurde bisher 29-mal zitiert (Crossref) und nennt 42 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Eusko Jaurlaritza, Spanish Government, ERDF A way of making Europe.
Abstract (Originalsprache)
This work presents a novel measurement method to characterize long-term and short-term variations of the LV grid impedance from 20 kHz to 10 MHz with configurable time, frequency and amplitude resolutions. The characterization of the grid access impedance in this frequency range is vital for the design and development of NB-PLC and BB-PLC technologies. The measurement system is valid for in-home, indoor cable networks and for the harsh conditions of the LV distribution grid, where a large input dynamic range and strong protection mechanisms against high-amplitude impulsive noises are required. Its accuracy is evaluated by comparison to a precision impedance meter for a wide set of impedance values, obtaining a maximum deviation within ±8%. First trials of the grid impedance sub-cycle variations caused by commercial appliances and for frequencies assigned to BB-PLC are also presented in this paper. The results demonstrate that the grid impedance is highly time-varying within the mains cycle, both in amplitude and phase. These first outcomes point at the need to evaluate the accumulative effects of sub-cycle variations in the LV distribution grid, so that equalization algorithms in the next BB-PLC technologies could be developed to overcome the impact of these fast variations.
Förderung
- Eusko Jaurlaritza
- Spanish Government
- ERDF A way of making Europe
Zitieren
APA
Fernández, I., Gallarreta, A., González-Ramos, J., Wright, P., Vega, D. D. L., Angulo, I., & Arrinda, A. (2023). Measurement System of the Mean and Sub-Cycle LV Grid Access Impedance From 20 kHz To 10 MHz. IEEE Transactions on Power Delivery, 38(3), 2204-2212. https://doi.org/10.1109/tpwrd.2023.3238647
Vancouver
Fernández I, Gallarreta A, González-Ramos J, Wright P, Vega DDL, Angulo I, et al. Measurement System of the Mean and Sub-Cycle LV Grid Access Impedance From 20 kHz To 10 MHz. IEEE Transactions on Power Delivery. 2023;38(3):2204-2212. doi:10.1109/tpwrd.2023.3238647
BibTeX
@article{Fernndez2023,
author = {Fernández, Igor and Gallarreta, Alexander and González-Ramos, Jon and Wright, Paul and Vega, David de la and Angulo, Itziar and Arrinda, Amaia},
title = {Measurement System of the Mean and Sub-Cycle LV Grid Access Impedance From 20 kHz To 10 MHz},
journal = {IEEE Transactions on Power Delivery},
year = {2023},
volume = {38},
number = {3},
pages = {2204--2212},
doi = {10.1109/tpwrd.2023.3238647}
}