Lightning Protection With a Differentiated Configuration of Arresters in a Distribution Network
IEEE Transactions on Power Delivery · 2023-02 · 38 (1) · 409-419
DOI: 10.1109/tpwrd.2022.3192482 ↗Kurz gefasst
Fachartikel in der Zeitschrift IEEE Transactions on Power Delivery, 2023-02. Verfasst von Jinxin Cao und 7 weiteren Autor:innen. Die Arbeit wurde bisher 38-mal zitiert (Crossref) und nennt 31 Literaturangaben. Gefördert von: Research Grants Council of the HKSAR, HK Polytechnic University.
Abstract (Originalsprache)
When concerning the installation and operation costs, it is always desirable to protect an overhead distribution network with a limited quantity of surge arresters (SAs). This paper presents a novel procedure for designing differentiated protection against lightning, by identifying appropriate positions for those SAs on the overhead line. Rather than the traditional flashover rate of a whole line, indices in terms of flashover numbers at individual poles and associated with possible stroke locations are introduced in this paper. Based on these flashover indices, a differentiated configuration of SAs can be identified using a selection strategy. After several rounds of selection, a differentiated SA protection scheme can be obtained, given by a pre-set quantity of SAs. In this procedure, a simplified probability-based approach is proposed to determine the flashover indices. By comparing the traditional Monte Carlo method, this approach can achieve a 10-fold increase in computational efficiency with reasonable accuracy. Two different selection strategies are introduced in this paper. Compared with the selection strategy using the flashover indices at individual poles, the selection strategy based on a group of poles is recommended because it yields a configuration with better lightning performance with the same quantity of SAs. This design procedure is applied to practical distribution networks with a shield wire and nearby structures. The influence of grounding impedance, a shield wire, and nearby structures is addressed. Finally, a generalized step-by-step procedure is provided to assist in a differentiated SA protection design.
Förderung
- Research Grants Council of the HKSAR
- HK Polytechnic University
Zitieren
APA
Cao, J., Du, Y., Ding, Y., Qi, R., Chen, M., Li, Z., Zhao, X., & Andreotti, A. (2023). Lightning Protection With a Differentiated Configuration of Arresters in a Distribution Network. IEEE Transactions on Power Delivery, 38(1), 409-419. https://doi.org/10.1109/tpwrd.2022.3192482
Vancouver
Cao J, Du Y, Ding Y, Qi R, Chen M, Li Z, et al. Lightning Protection With a Differentiated Configuration of Arresters in a Distribution Network. IEEE Transactions on Power Delivery. 2023;38(1):409-419. doi:10.1109/tpwrd.2022.3192482
BibTeX
@article{Cao2023,
author = {Cao, Jinxin and Du, Yaping and Ding, Yuxuan and Qi, Ruihan and Chen, Mingli and Li, Zhe and Zhao, Xiangen and Andreotti, Amedeo},
title = {Lightning Protection With a Differentiated Configuration of Arresters in a Distribution Network},
journal = {IEEE Transactions on Power Delivery},
year = {2023},
volume = {38},
number = {1},
pages = {409--419},
doi = {10.1109/tpwrd.2022.3192482}
}