EUVIMEDEUVIMED entdecken
Crossref

PLL Synchronization Transient Stability Analysis of a Weak-Grid Connected VSC During Asymmetric Faults

Zhi Wang, Li Guo, Xialin Li, Xiulan Pang, Xiaofeng Li, Xu Zhou, Chengshan Wang

IEEE Transactions on Power Electronics · 2024-02 · 39 (2) · 2140-2154

DOI: 10.1109/tpel.2023.3333808 ↗

Kurz gefasst

Fachartikel in der Zeitschrift IEEE Transactions on Power Electronics, 2024-02. Verfasst von Zhi Wang und 6 weiteren Autor:innen. Die Arbeit wurde bisher 27-mal zitiert (Crossref) und nennt 31 Literaturangaben. Gefördert von: National Key R&D Program of China, Academician Innovation Platform Project of Hainan Province, National Natural Science Foundation of China.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

During asymmetric faults, the coupling between positive and negative (PN) sequences significantly affects the phase-locked-loop (PLL) synchronization transient stability (PSTS) of a weak-grid connected voltage source converter (WG-VSC). However, little literature is on analyzing the PSTS while considering PN sequence coupling. This article has analyzed the PSTS of the WG-VSC system considering PN sequence coupling under asymmetric faults for the first time. First, the Takagi–Sugeno method is adopted to construct the largest estimated domain of attraction (LEDA) at an equilibrium point of the system during asymmetric faults. This LEDA enables quantitative analysis of PLL synchronization transient instability phenomena. Furthermore, from the point of view of ensuring the PSTS, the feasible region of PN currents (FR-PNC) of the system during asymmetric faults has been obtained. In addition, an algorithm is proposed to visualize this 4-D FR-PNC in 2-D space. Finally, the theoretical analysis is validated by time domain experiments conducted on the RT-Box hardware-in-the-loop experimental platform.

Förderung

  • National Key R&D Program of China
  • Academician Innovation Platform Project of Hainan Province
  • National Natural Science Foundation of China

Zitieren

APA

Wang, Z., Guo, L., Li, X., Pang, X., Li, X., Zhou, X., & Wang, C. (2024). PLL Synchronization Transient Stability Analysis of a Weak-Grid Connected VSC During Asymmetric Faults. IEEE Transactions on Power Electronics, 39(2), 2140-2154. https://doi.org/10.1109/tpel.2023.3333808

Vancouver

Wang Z, Guo L, Li X, Pang X, Li X, Zhou X, et al. PLL Synchronization Transient Stability Analysis of a Weak-Grid Connected VSC During Asymmetric Faults. IEEE Transactions on Power Electronics. 2024;39(2):2140-2154. doi:10.1109/tpel.2023.3333808

BibTeX
@article{Wang2024,
  author = {Wang, Zhi and Guo, Li and Li, Xialin and Pang, Xiulan and Li, Xiaofeng and Zhou, Xu and Wang, Chengshan},
  title = {PLL Synchronization Transient Stability Analysis of a Weak-Grid Connected VSC During Asymmetric Faults},
  journal = {IEEE Transactions on Power Electronics},
  year = {2024},
  volume = {39},
  number = {2},
  pages = {2140--2154},
  doi = {10.1109/tpel.2023.3333808}
}
Kostenlos starten →