EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Detection of Partial Discharge in CVT Capacitive Units Based on Abrupt Changes in Voltage Ratio Error and Phase Angle Error

Dexu Zou, Weiju Dai, Zhihu Hong, Qingyun Min, Haoruo Sun, Guangde Song

IEEE Access · 2026 · 14 · 96311-96321

DOI: 10.1109/access.2026.3705739 ↗

Kurz gefasst

Fachartikel in der Zeitschrift IEEE Access, 2026. Verfasst von Dexu Zou und 5 weiteren Autor:innen. Die Arbeit nennt 24 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: China Southern Power Grid Yunnan Power Grid Company Ltd..

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

As a critical component in power systems, the insulation degradation of Capacitive Voltage Transformers (CVTs) caused by partial discharge poses a direct threat to grid safety and stable operation. To address the limitations of conventional detection methods, such as limited interference immunity and insufficient diagnostic accuracy, this paper proposes a CVT partial discharge state identification method that integrates voltage ratio error and phase angle error abrupt change analysis. By synchronously acquiring the secondary voltage signal of the CVT and the reference voltage signal from the bus potential transformer (PT) secondary side, the method accurately computes the voltage ratio error and phase angle error. A deterministic relationship between the abrupt change direction of these errors and the capacitance variation caused by partial discharge is derived from circuit theory, clarifying the underlying mechanisms. A high-frequency spectral energy ratio (HFSER) is introduced to establish a multi-dimensional identification system, effectively eliminating interference from grid voltage fluctuations. A simulation platform is established in MATLAB/Simulink to validate the method’s effectiveness. The simulation results confirm the theoretical analysis, achieving a four-class state identification accuracy of 97.07% on the simulated test set in CVT capacitive units. The proposed approach enables early fault warning and arm-level discharge identification, offering reliable technical support for condition-based maintenance of power equipment.

Förderung

  • China Southern Power Grid Yunnan Power Grid Company Ltd.

Zitieren

APA

Zou, D., Dai, W., Hong, Z., Min, Q., Sun, H., & Song, G. (2026). Detection of Partial Discharge in CVT Capacitive Units Based on Abrupt Changes in Voltage Ratio Error and Phase Angle Error. IEEE Access, 14, 96311-96321. https://doi.org/10.1109/access.2026.3705739

Vancouver

Zou D, Dai W, Hong Z, Min Q, Sun H, Song G. Detection of Partial Discharge in CVT Capacitive Units Based on Abrupt Changes in Voltage Ratio Error and Phase Angle Error. IEEE Access. 2026;14:96311-96321. doi:10.1109/access.2026.3705739

BibTeX
@article{Zou2026,
  author = {Zou, Dexu and Dai, Weiju and Hong, Zhihu and Min, Qingyun and Sun, Haoruo and Song, Guangde},
  title = {Detection of Partial Discharge in CVT Capacitive Units Based on Abrupt Changes in Voltage Ratio Error and Phase Angle Error},
  journal = {IEEE Access},
  year = {2026},
  volume = {14},
  pages = {96311--96321},
  doi = {10.1109/access.2026.3705739}
}
Kostenlos starten →