EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Study on Switchgear Partial-Discharge Localization Based on the 3D-ROOT-MUSIC Algorithm

Peng Zhang, Chang Liu, Jian Zhang, Yue Wang, Zhen Zhang, Zhaoyang Ren, Yanling Lv, Huiyu Huang, Zhenjia Li

IEEE Access · 2026 · 14 · 79596-79608

DOI: 10.1109/access.2026.3695079 ↗

Kurz gefasst

Fachartikel in der Zeitschrift IEEE Access, 2026. Verfasst von Peng Zhang und 8 weiteren Autor:innen. Die Arbeit nennt 19 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: 2025 Science and Technology Project of State Grid Heilongjiang Electric Power Company Ltd..

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Ultrasonic-based partial-discharge (PD) detection has attracted considerable attention in the power industry. When the ROOT-MUSIC algorithm is used to detect PD sources in switchgear, the angle search can only be performed within the plane of a one-dimensional linear array, resulting in a limited direction-finding range and angular blind zones. To address these limitations, a 3D-ROOT-MUSIC algorithm is proposed. By adopting a dual dimensionality-reduction strategy, the proposed 3D-ROOT-MUSIC algorithm decomposes a three-dimensional polynomial into three one-dimensional polynomials, thereby overcoming the difficulty of solving the 3D rooting polynomial and enabling applicability to three-dimensional arrays. Simulation results based on 100 Monte Carlo trials and root-mean-square error (RMSE) evaluations under different signal-to-noise ratio (SNR) conditions indicate that the proposed algorithm achieves high direction-finding accuracy, a wide angular coverage, and strong interference robustness. Finally, a 27-element cubic array was built using IM73D122V01 digital microphones to conduct PD-source detection experiments in a switchgear scenario; across 11 direction-finding test groups, the azimuth and elevation residuals fall within −0.3° to 0.4°, and the RMSE remains stable between 0.3° and 0.5°, which verifies the effectiveness and accuracy of the 3D-ROOT-MUSIC algorithm for PD-source detection in switchgear.

Förderung

  • 2025 Science and Technology Project of State Grid Heilongjiang Electric Power Company Ltd.

Zitieren

APA

Zhang, P., Liu, C., Zhang, J., Wang, Y., Zhang, Z., Ren, Z., Lv, Y., Huang, H., & Li, Z. (2026). Study on Switchgear Partial-Discharge Localization Based on the 3D-ROOT-MUSIC Algorithm. IEEE Access, 14, 79596-79608. https://doi.org/10.1109/access.2026.3695079

Vancouver

Zhang P, Liu C, Zhang J, Wang Y, Zhang Z, Ren Z, et al. Study on Switchgear Partial-Discharge Localization Based on the 3D-ROOT-MUSIC Algorithm. IEEE Access. 2026;14:79596-79608. doi:10.1109/access.2026.3695079

BibTeX
@article{Zhang2026,
  author = {Zhang, Peng and Liu, Chang and Zhang, Jian and Wang, Yue and Zhang, Zhen and Ren, Zhaoyang and Lv, Yanling and Huang, Huiyu and Li, Zhenjia},
  title = {Study on Switchgear Partial-Discharge Localization Based on the 3D-ROOT-MUSIC Algorithm},
  journal = {IEEE Access},
  year = {2026},
  volume = {14},
  pages = {79596--79608},
  doi = {10.1109/access.2026.3695079}
}