Partial Discharge Detection Technology for Switchgear Based on Near-Field Detection
Electronics · 09.01.2023 · 12 (2) · 336
DOI: 10.3390/electronics12020336 ↗Kurz gefasst
Fachartikel in der Zeitschrift Electronics, online erschienen am 09.01.2023. Verfasst von Chunguang Suo und 5 weiteren Autor:innen. Die Arbeit wurde bisher 13-mal zitiert (Crossref) und nennt 34 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Research and development of new smart sensor technology to promote the development of green energy, Research and development of key technologies for conformal implantation of new intelligent power sensing for power grid main equipment.
Abstract (Originalsprache)
In view of the fact that the partial discharge (PD) signal energy is mainly concentrated below hundreds of megahertz, the ultra-high frequency part of the energy is weak, and the interior space of the switchgear is narrow, this paper proposes a new method for PD detection of the switchgear based on near-field detection. Firstly, based on the principle of PD, the field characteristics of the signal in the switchgear are analyzed. After that, the probe is designed with an electric small loop structure. Based on its equivalent circuit, its measurement principle and amplitude frequency characteristics are analyzed. The influence of probe size and material on amplitude frequency characteristics is obtained by using simulation software High Frequency Structure Simulator (HFSS), and the probe parameters suitable for PD detection in the switchgear are determined. Finally, the performance of the probe is measured by network analyzer, and the PD signal is tested on the simulated PD test platform. The results show that the probe works in the frequency band of 10–200 MHz and can receive PD signals containing more energy information. In the operating frequency band, the reflection coefficient of the probe port is very large, and its interference to the signal near field is particularly small. The probe also has good frequency response characteristics, and the fluctuation in the frequency band is less than 5 dB, which can obtain more accurate PD signal characteristics in subsequent processing. In addition, the probe is passive, with dimensions of 166 mm in length, 104 mm in width, and 2 mm in thickness, which is suitable for placing in the switchgear with small internal space. The results of PD receiving test show that the probe can reflect the occurrence of PD remarkably and accurately.
Förderung
- Research and development of new smart sensor technology to promote the development of green energy
- Research and development of key technologies for conformal implantation of new intelligent power sensing for power grid main equipment
Zitieren
APA
Suo, C., Zhao, J., Wu, X., Xu, Z., Zhang, W., & He, M. (2023). Partial Discharge Detection Technology for Switchgear Based on Near-Field Detection. Electronics, 12(2), 336. https://doi.org/10.3390/electronics12020336
Vancouver
Suo C, Zhao J, Wu X, Xu Z, Zhang W, He M. Partial Discharge Detection Technology for Switchgear Based on Near-Field Detection. Electronics. 2023;12(2):336. doi:10.3390/electronics12020336
BibTeX
@article{Suo2023,
author = {Suo, Chunguang and Zhao, Jingjing and Wu, Xuehua and Xu, Zhipeng and Zhang, Wenbin and He, Mingxing},
title = {Partial Discharge Detection Technology for Switchgear Based on Near-Field Detection},
journal = {Electronics},
year = {2023},
volume = {12},
number = {2},
pages = {336},
doi = {10.3390/electronics12020336}
}