Uncertainties in exposure predictions arising from point measurements of carbon dioxide in classroom environments
Journal of The Royal Society Interface · 2024
DOI: 10.1098/rsif.2024.0270 ↗Kurz gefasst
Fachartikel in der Zeitschrift Journal of The Royal Society Interface, 2024. Verfasst von Carolanne V M Vouriot und 2 weiteren Autor:innen. Beteiligte Einrichtung: School of Mechanical, Aerospace and Civil Engineering, University of Sheffield, Mappin Street, Sheffield S1 3JD, UK. Hauptthemen laut MEDLINE: Carbon Dioxide, Ventilation. Die Arbeit wurde bisher 2-mal zitiert (Crossref) und nennt 21 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0). Gefördert von: Engineering and Physical Sciences Research Council.
Abstract (Originalsprache)
Predictions of airborne infection risk can be made based on the fraction of rebreathed air inferred from point measurements of carbon dioxide (CO 2 ). We investigate the extent to which environmental factors, particularly spatial variations due to the ventilation provision, affect the uncertainty in these predictions. Spatial variations are expected to be especially problematic in naturally ventilated spaces, which include the majority of classrooms in the UK. An idealized classroom, broadly representative of the physics of (buoyancy-driven) displacement ventilation, is examined using computational fluid dynamics, with different ventilation configurations. Passive tracers are used to model both the CO 2 generated by all 32 occupants and the breath of a single infectious individual (located in nine different regions). The distribution of infected breath is shown to depend strongly on the distance from the release location but is also affected by the pattern of the ventilating flow, including the presence of stagnating regions. However, far-field exposure predictions based on single point measurements of CO 2 within the breathing zone are shown to rarely differ from the actual exposure to infected breath by more than a factor of two—we argue this uncertainty is small compared with other uncertainties inherent in modelling airborne infection risk.
Schlagwörter
MeSH-Schlagwörter (MEDLINE)
Stichwörter der Autor:innen
Substanzen
Autor:innen und Institutionen
- School of Mechanical, Aerospace and Civil Engineering, University of Sheffield, Mappin Street, Sheffield S1 3JD, UK.
- Department of Applied Mathematics and Theoretical Physics, Centre for Mathematical Sciences, University of Cambridge, Wilberforce Road, Cambridge CB3 0WA, UK.
- Department of Civil and Environmental Engineering, Skempton Building, South Kensington Campus, Imperial College London, London SW7 2BX, UK.
ORCID-Profile: Carolanne V M Vouriot, Henry C Burridge
Förderung
- Engineering and Physical Sciences Research Council
Zitieren
APA
Vouriot, C. V. M., van Reeuwijk, M., & Burridge, H. C. (2024). Uncertainties in exposure predictions arising from point measurements of carbon dioxide in classroom environments. Journal of The Royal Society Interface. https://doi.org/10.1098/rsif.2024.0270
Vancouver
Vouriot CVM, van Reeuwijk M, Burridge HC. Uncertainties in exposure predictions arising from point measurements of carbon dioxide in classroom environments. Journal of The Royal Society Interface. 2024. doi:10.1098/rsif.2024.0270
BibTeX
@article{Vouriot2024,
author = {Vouriot, Carolanne V M and van Reeuwijk, Maarten and Burridge, Henry C},
title = {Uncertainties in exposure predictions arising from point measurements of carbon dioxide in classroom environments},
journal = {Journal of The Royal Society Interface},
year = {2024},
doi = {10.1098/rsif.2024.0270}
}