Spectral characteristics of FBG sensors for high-speed generator rotor temperature monitoring: insights into centrifugal effects
Measurement Science and Technology · 19.06.2026 · 37 (25) · 255002
DOI: 10.1088/1361-6501/ae7396 ↗Kurz gefasst
Fachartikel in der Zeitschrift Measurement Science and Technology, online erschienen am 22.06.2026. Verfasst von Sitong Chen und 3 weiteren Autor:innen. Die Arbeit nennt 27 Literaturangaben. Gefördert von: JD project of Hubei province.
Abstract (Originalsprache)
This work investigates the spectral behavior of fiber Bragg grating (FBG) sensors subjected to centrifugal effects for online heat monitoring in high-speed generator rotors. A quasi-distributed measurement system using optical spatial coupling is proposed, along with a theoretical model of stress-induced birefringence in rotating FBGs. The model reveals that centrifugal loading causes reflection peak splitting and bidirectional wavelength shifts, with the long-wavelength shift approximately an order of magnitude larger than the short-wavelength shift. Both shifts scale with rotor radius, square of rotational speed, and FBG coating thickness. Parametric analysis shows that reducing coating thickness effectively suppresses these shifts. An optimal polyimide thickness of approximately 20 μm is identified, balancing optical and mechanical performance. Under this condition, for a 15 cm rotor radius and speeds below 10 000 rpm, the center wavelength shift remains below 0.18 pm, corresponding to a maximum temperature error of approximately 0.02 °C. Experiments on a 3000 rpm generator rotor successfully captured dynamic temperature distributions. During startup, the pole region temperature rose sharply within 25 s, reaching a maximum of approximately 14 °C, followed by a rapid decline then gradual increase—consistent with armature loss behavior. Over 133 min of rated operation, temperature increased nearly linearly before slowing, reaching 82.2 °C. Under braking, a maximum rise of about 5.2 °C was observed. Spatially, temperature decreases from the rotor center toward both ends, with the pole region 0–11.6 °C warmer than the bracket region. The mid-to-rear pole section during braking is identified as a hotspot high-risk zone. This study clarifies FBG spectral response under rotation, quantifies centrifugal-induced measurement errors, and validates FBG-based rotor temperature monitoring as a feasible and reliable approach.
Förderung
- JD project of Hubei province
Zitieren
APA
Chen, S., Hou, M., Wang, D., & Gu, H. (2026). Spectral characteristics of FBG sensors for high-speed generator rotor temperature monitoring: insights into centrifugal effects. Measurement Science and Technology, 37(25), 255002. https://doi.org/10.1088/1361-6501/ae7396
Vancouver
Chen S, Hou M, Wang D, Gu H. Spectral characteristics of FBG sensors for high-speed generator rotor temperature monitoring: insights into centrifugal effects. Measurement Science and Technology. 2026;37(25):255002. doi:10.1088/1361-6501/ae7396
BibTeX
@article{Chen2026,
author = {Chen, Sitong and Hou, Ming and Wang, Dianyu and Gu, Hongcan},
title = {Spectral characteristics of FBG sensors for high-speed generator rotor temperature monitoring: insights into centrifugal effects},
journal = {Measurement Science and Technology},
year = {2026},
volume = {37},
number = {25},
pages = {255002},
doi = {10.1088/1361-6501/ae7396}
}
EUVIMED