EUVIMEDEUVIMED entdecken
Open Access · CC BY 4.0

Prestrike characteristics and dynamic dielectric breakdown mechanism of double-break vacuum circuit breakers under AC and DC voltages

Hannan Shan, Yun Geng, Jing Yan, Yiwen Chen, Pu Chen, Yingsan Geng, Zhiyuan Liu

AIP Advances · 01.11.2026 · 16 (11)

DOI: 10.1063/5.0352220 ↗

Kurz gefasst

Fachartikel in der Zeitschrift AIP Advances, online erschienen am 12.11.2026. Verfasst von Hannan Shan und 6 weiteren Autor:innen. Die Arbeit nennt 25 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Understanding the prestrike characteristics of vacuum circuit breakers is essential for phase-controlled closing and insulation design. Double-break vacuum circuit breakers (DBVCBs) are used in reactive power compensation, but most studies of their prestrike behavior have focused on DC conditions. Systematic comparisons with AC operation remain limited. This study compares the prestrike characteristics of a DBVCB at 20 and 30 kV under DC and power-frequency AC voltages, with AC levels specified as RMS values. Prestrike gaps, voltages, and average gap fields are characterized using Weibull fits, and macroscopic electric field distributions are simulated in ANSYS Maxwell. The AC statistical comparison is restricted to events near the positive voltage peak. At 30 kV, the median prestrike gap on the high-voltage side is 1.26 mm under AC, compared with 0.57 mm under DC. As the applied voltage increases, the median average prestrike field increases under DC but decreases under AC. The results highlight the coupling between voltage phase and contact motion during AC closing, while microscopic initiation mechanisms remain to be verified. These findings inform insulation design and phase-controlled closing strategies for DBVCBs.

Zitieren

APA

Shan, H., Geng, Y., Yan, J., Chen, Y., Chen, P., Geng, Y., & Liu, Z. (2026). Prestrike characteristics and dynamic dielectric breakdown mechanism of double-break vacuum circuit breakers under AC and DC voltages. AIP Advances, 16(11). https://doi.org/10.1063/5.0352220

Vancouver

Shan H, Geng Y, Yan J, Chen Y, Chen P, Geng Y, et al. Prestrike characteristics and dynamic dielectric breakdown mechanism of double-break vacuum circuit breakers under AC and DC voltages. AIP Advances. 2026;16(11). doi:10.1063/5.0352220

BibTeX
@article{Shan2026,
  author = {Shan, Hannan and Geng, Yun and Yan, Jing and Chen, Yiwen and Chen, Pu and Geng, Yingsan and Liu, Zhiyuan},
  title = {Prestrike characteristics and dynamic dielectric breakdown mechanism of double-break vacuum circuit breakers under AC and DC voltages},
  journal = {AIP Advances},
  year = {2026},
  volume = {16},
  number = {11},
  doi = {10.1063/5.0352220}
}
Kostenlos starten →