EUVIMEDEUVIMED entdecken
Open Access · CC BY-NC-ND 4.0

Post‐Arc Transient Dielectric Recovery Characteristics of Vacuum Interrupter in the Large‐Capacity Generator Circuit Breaker

Xiangyu Han, Fei Yang, Yili Chen, Yunqi Wang, Chenle Zhai, Xuliang Zhao, Zhaowei Diao, Yi Wu, Mingzhe Rong

High Voltage · 2026-08 · 11 (4) · 999-1010

DOI: 10.1049/hve2.70153 ↗

Kurz gefasst

Fachartikel in der Zeitschrift High Voltage, online erschienen am 11.02.2026. Verfasst von Xiangyu Han und 8 weiteren Autor:innen. Die Arbeit wurde bisher 4-mal zitiert (Crossref) und nennt 33 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY-NC-ND 4.0). Gefördert von: National Key Research and Development Program of China, National Natural Science Foundation of China.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Large‐capacity generator circuit breaker (GCB) based on vacuum interrupter technology is the key power equipment to ensure the safe operation of the power system. When the short‐circuit current was forced to cross zero, the large‐capacity GCB was difficult to generate a zero‐voltage environment through freewheeling, the vacuum interrupter (VI) would immediately withstand the transient recovery voltage (TRV), and there was a lack of research on the post‐arc transient dielectric recovery characteristics. First, an experimental platform for transient dielectric recovery characteristics was built, which was capable of generating TRV quickly after current‐zero with the voltage rise rate (d u /d t ) of about 20 kV/μs. The large current post‐arc dielectric recovery tolerance experiments with the peak current of 100 kA were carried out, and the post‐arc tolerance process was divided into three modes according to the TRV waveform. The influence of arcing time, residual current and current change rate (d i /d t ) on the transient dielectric recovery characteristics was investigated. Next, we found that the transient dielectric recovery of VI under the same conditions was characterised by dispersion. The influence mechanisms of ‘active regulation of the vacuum arc’ and ‘consistency of the arcing process’ on the dispersion of the transient dielectric recovery were studied in detail. The ‘safety boundary’ consisting of the minimum of dielectric recovery strength was analysed, and the optimal arcing control strategy was proposed. The design basis of the circuit breaker was obtained. Finally, a prototype GCB based on vacuum six‐breakers in parallel and current transfer was developed, and the large short‐circuit current had been successfully broken, which verified the post‐arc transient breaking reliability of the VI. The conclusions will lay the foundation for the engineering application of high‐capacity GCB.

Förderung

  • National Key Research and Development Program of China
  • National Natural Science Foundation of China

Zitieren

APA

Han, X., Yang, F., Chen, Y., Wang, Y., Zhai, C., Zhao, X., Diao, Z., Wu, Y., & Rong, M. (2026). Post‐Arc Transient Dielectric Recovery Characteristics of Vacuum Interrupter in the Large‐Capacity Generator Circuit Breaker. High Voltage, 11(4), 999-1010. https://doi.org/10.1049/hve2.70153

Vancouver

Han X, Yang F, Chen Y, Wang Y, Zhai C, Zhao X, et al. Post‐Arc Transient Dielectric Recovery Characteristics of Vacuum Interrupter in the Large‐Capacity Generator Circuit Breaker. High Voltage. 2026;11(4):999-1010. doi:10.1049/hve2.70153

BibTeX
@article{Han2026,
  author = {Han, Xiangyu and Yang, Fei and Chen, Yili and Wang, Yunqi and Zhai, Chenle and Zhao, Xuliang and Diao, Zhaowei and Wu, Yi and Rong, Mingzhe},
  title = {Post‐Arc Transient Dielectric Recovery Characteristics of Vacuum Interrupter in the Large‐Capacity Generator Circuit Breaker},
  journal = {High Voltage},
  year = {2026},
  volume = {11},
  number = {4},
  pages = {999--1010},
  doi = {10.1049/hve2.70153}
}
Kostenlos starten →