EUVIMEDEUVIMED entdecken
Crossref

Residual‐Free Excitation Inrush Suppression for Three‐Phase Interconnected Circuit Breakers

Wenchao Chu, Feng Xing, Qiong Wang, Tao Chen, Lei Zhao, Yang Ji, Bingjie Dou

IEEJ Transactions on Electrical and Electronic Engineering · 28.05.2026

DOI: 10.1002/tee.70338 ↗

Kurz gefasst

Fachartikel in der Zeitschrift IEEJ Transactions on Electrical and Electronic Engineering, online erschienen am 28.05.2026. Verfasst von Wenchao Chu und 6 weiteren Autor:innen. Die Arbeit nennt 22 Literaturangaben.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

As the cornerstone equipment of power systems, transformers may generate magnetizing inrush currents during no‐load energization, potentially causing equipment damage and system instability, which constitutes a critical technical challenge requiring urgent resolution. This paper proposes a novel synchronized phase‐selective closing strategy applicable to three‐phase gang‐operated circuit breakers that eliminates the need for precise residual flux measurement. Through comprehensive analysis of the inrush current generation mechanism and core residual flux variation patterns, we reveal that the three‐phase residual fluxes form a slowly rotating vector triangle that stabilizes when the post‐opening voltage decays to a critical threshold. Building on this discovery, the proposed method employs the residual flux vector at the opening instant as a reference and initiates breaker closing at the identical phase angle after integer power‐frequency cycles, ensuring perfect alignment between the anticipated flux and residual flux vector to prevent deep core saturation. Theoretical analysis, simulation studies, and experimental verification collectively demonstrate that compared with conventional flux‐difference function methods, the proposed strategy achieves superior inrush current suppression while significantly reducing dependence on residual flux measurement accuracy. This breakthrough substantially enhances both engineering applicability and operational reliability in practical power system applications. © 2026 Institute of Electrical Engineers of Japan and Wiley Periodicals LLC.

Zitieren

APA

Chu, W., Xing, F., Wang, Q., Chen, T., Zhao, L., Ji, Y., & Dou, B. (2026). Residual‐Free Excitation Inrush Suppression for Three‐Phase Interconnected Circuit Breakers. IEEJ Transactions on Electrical and Electronic Engineering. https://doi.org/10.1002/tee.70338

Vancouver

Chu W, Xing F, Wang Q, Chen T, Zhao L, Ji Y, et al. Residual‐Free Excitation Inrush Suppression for Three‐Phase Interconnected Circuit Breakers. IEEJ Transactions on Electrical and Electronic Engineering. 2026. doi:10.1002/tee.70338

BibTeX
@article{Chu2026,
  author = {Chu, Wenchao and Xing, Feng and Wang, Qiong and Chen, Tao and Zhao, Lei and Ji, Yang and Dou, Bingjie},
  title = {Residual‐Free Excitation Inrush Suppression for Three‐Phase Interconnected Circuit Breakers},
  journal = {IEEJ Transactions on Electrical and Electronic Engineering},
  year = {2026},
  doi = {10.1002/tee.70338}
}
Kostenlos starten →