EUVIMEDEUVIMED entdecken
Crossref

Analysis of Surge Arrester Burnout Faults on Actual Distribution Line in Summer

Chiharu Sakakibara, Koji Michishita, Koji Takano, Hidehiro Nakata, Michihiro Matsui

IEEJ Transactions on Electrical and Electronic Engineering · 2026-06 · 21 (6) · 948-955

DOI: 10.1002/tee.70282 ↗

Kurz gefasst

Fachartikel in der Zeitschrift IEEJ Transactions on Electrical and Electronic Engineering, online erschienen am 16.03.2026. Verfasst von Chiharu Sakakibara und 4 weiteren Autor:innen. Die Arbeit nennt 25 Literaturangaben.

AbstractBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

Analysis of actual outages is essential for efficient lightning‐protection design. In this study, we estimate strokes that cause surge arrester burnout faults by considering not only the distance from the fault position to the stroke position estimated by a lightning location system but also the estimated peak current. Different configurations of the distribution line experiencing surge arrester damage are observed: various types of surge arresters are installed at the lightning striking pole, and the low‐voltage power distribution line is installed below the medium‐voltage line in some cases. The effect of this variation on the possibility of surge arrester damage is examined via numerical calculation. Results show that the variation in the withstand capability of surge arresters and the presence of appendant wires should be considered to reproduce surge arrester burnout faults on actual distribution lines in the summer. © 2026 Institute of Electrical Engineers of Japan and Wiley Periodicals LLC.

Zitieren

APA

Sakakibara, C., Michishita, K., Takano, K., Nakata, H., & Matsui, M. (2026). Analysis of Surge Arrester Burnout Faults on Actual Distribution Line in Summer. IEEJ Transactions on Electrical and Electronic Engineering, 21(6), 948-955. https://doi.org/10.1002/tee.70282

Vancouver

Sakakibara C, Michishita K, Takano K, Nakata H, Matsui M. Analysis of Surge Arrester Burnout Faults on Actual Distribution Line in Summer. IEEJ Transactions on Electrical and Electronic Engineering. 2026;21(6):948-955. doi:10.1002/tee.70282

BibTeX
@article{Sakakibara2026,
  author = {Sakakibara, Chiharu and Michishita, Koji and Takano, Koji and Nakata, Hidehiro and Matsui, Michihiro},
  title = {Analysis of Surge Arrester Burnout Faults on Actual Distribution Line in Summer},
  journal = {IEEJ Transactions on Electrical and Electronic Engineering},
  year = {2026},
  volume = {21},
  number = {6},
  pages = {948--955},
  doi = {10.1002/tee.70282}
}
Kostenlos starten →