Research on Vibration Characteristic Analysis and Fault Diagnosis Method of Oil‐Immersed Transformer Based on Multi‐Physics Coupling
IEEJ Transactions on Electrical and Electronic Engineering · 2024-10 · 19 (10) · 1621-1630
DOI: 10.1002/tee.24120 ↗Kurz gefasst
Fachartikel in der Zeitschrift IEEJ Transactions on Electrical and Electronic Engineering, online erschienen am 28.05.2024. Verfasst von Fating Yuan und 5 weiteren Autor:innen. Die Arbeit wurde bisher 10-mal zitiert (Crossref) und nennt 24 Literaturangaben. Gefördert von: National Natural Science Foundation of China.
Abstract (Originalsprache)
The oil‐immersed transformer is a crucial power equipment in power system, which is prone to abnormality or failure under long running. In order to improve the level of operation and maintenance and ensure the safe and reliable operation of the power grid, it is necessary to diagnose the fault of the oil‐immersed transformer in time. Most of the traditional fault vibration methods are off‐line detection, and are easily disturbed by mechanical deterioration. In order to solve the above problems, this paper established a 3D electromagnetic and stress coupling simulation model of oil‐immersed transformer by finite element simulation software. The vibration characteristics of oil‐immersed transformer core winding are obtained, and at the same time, this paper obtained the vibration signals at different positions on transformer core winding and oil tank. According to the vibration signal of the transformer, the best measuring point position of the tank wall is proposed to accurately reflect the vibration characteristics of the transformer. The signal data is preprocessed by CEEMDAN decomposition method, and the signal data is classified by GWO‐BP composite classification algorithm. This paper proposed an online transformer fault diagnosis method based on vibration signal, which achieves the purpose of accurately diagnosing oil‐immersed transformer faults. The test results show that in the case of oil‐immersed transformers the accuracy of the proposed transformer fault diagnosis method is more than 93%, which provides important guiding significance for the safe and stable operation of the transformer. © 2024 Institute of Electrical Engineers of Japan and Wiley Periodicals LLC.
Förderung
- National Natural Science Foundation of China
Zitieren
APA
Yuan, F., Yan, Z., Zhang, R., Yang, Y., Jian, S., & Tang, B. (2024). Research on Vibration Characteristic Analysis and Fault Diagnosis Method of Oil‐Immersed Transformer Based on Multi‐Physics Coupling. IEEJ Transactions on Electrical and Electronic Engineering, 19(10), 1621-1630. https://doi.org/10.1002/tee.24120
Vancouver
Yuan F, Yan Z, Zhang R, Yang Y, Jian S, Tang B. Research on Vibration Characteristic Analysis and Fault Diagnosis Method of Oil‐Immersed Transformer Based on Multi‐Physics Coupling. IEEJ Transactions on Electrical and Electronic Engineering. 2024;19(10):1621-1630. doi:10.1002/tee.24120
BibTeX
@article{Yuan2024,
author = {Yuan, Fating and Yan, Zhiwei and Zhang, Renjie and Yang, Yi and Jian, Shengkai and Tang, Bo},
title = {Research on Vibration Characteristic Analysis and Fault Diagnosis Method of Oil‐Immersed Transformer Based on Multi‐Physics Coupling},
journal = {IEEJ Transactions on Electrical and Electronic Engineering},
year = {2024},
volume = {19},
number = {10},
pages = {1621--1630},
doi = {10.1002/tee.24120}
}