Traditional fault diagnosis methods for mineral oil‐immersed power transformer based on dissolved gas analysis: Past, present and future
IET Nanodielectrics · 2024-09 · 7 (3) · 97-130
DOI: 10.1049/nde2.12082 ↗Kurz gefasst
Fachartikel in der Zeitschrift IET Nanodielectrics, online erschienen am 22.04.2024. Verfasst von Arnaud Nanfak und 5 weiteren Autor:innen. Die Arbeit wurde bisher 72-mal zitiert (Crossref) und nennt 116 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY-ND 4.0).
Abstract (Originalsprache)
A key factor in ensuring the efficient and safe operation of power transformers is the early and accurate diagnosis of incipient faults. Among the tools available to achieve this goal, dissolved gas analysis (DGA) is widely used by power transformers' maintenance professionals. It is a preventive maintenance tool, used for condition monitoring, fault diagnosis and unplanned outage prevention. With the development of artificial intelligence (AI), many intelligent‐based methods using AI tools have been proposed in the literature for DGA data interpretation. Although these methods achieve high diagnostic accuracies and improve DGA efficiency, they are generally complicated and the research documented in these publications is difficult to replicate. Traditional DGA‐based methods are simple, easy to understand and implement, and widely used by power transformers' maintenance professionals. Many methods proposed in recent years overcome the limitations of the pioneer methods and are increasingly effective. The authors present a detailed and comprehensive literature review of the traditional DGA‐based methods for mineral oil‐immersed power transformer faults diagnosis. This review also addresses ways to improve the efficiency of the available traditional methods. Some pitfalls that need to be taken into account to improve the efficiency of the DGA‐based diagnostic methods are also presented.
Zitieren
APA
Nanfak, A., Samuel, E., Fofana, I., Meghnefi, F., Ngaleu, M. G., & Kom, C. H. (2024). Traditional fault diagnosis methods for mineral oil‐immersed power transformer based on dissolved gas analysis: Past, present and future. IET Nanodielectrics, 7(3), 97-130. https://doi.org/10.1049/nde2.12082
Vancouver
Nanfak A, Samuel E, Fofana I, Meghnefi F, Ngaleu MG, Kom CH. Traditional fault diagnosis methods for mineral oil‐immersed power transformer based on dissolved gas analysis: Past, present and future. IET Nanodielectrics. 2024;7(3):97-130. doi:10.1049/nde2.12082
BibTeX
@article{Nanfak2024,
author = {Nanfak, Arnaud and Samuel, Eke and Fofana, Issouf and Meghnefi, Fethi and Ngaleu, Martial Gildas and Kom, Charles Hubert},
title = {Traditional fault diagnosis methods for mineral oil‐immersed power transformer based on dissolved gas analysis: Past, present and future},
journal = {IET Nanodielectrics},
year = {2024},
volume = {7},
number = {3},
pages = {97--130},
doi = {10.1049/nde2.12082}
}
EUVIMED