The Impact of High Voltage Power Transformer Base Design on Bushing Seismic Amplification
Earthquake Engineering & Structural Dynamics · 2026-08 · 55 (10) · 2396-2408
DOI: 10.1002/eqe.70177 ↗Kurz gefasst
Fachartikel in der Zeitschrift Earthquake Engineering & Structural Dynamics, online erschienen am 12.05.2026. Verfasst von Jon Bender und 3 weiteren Autor:innen. Die Arbeit nennt 22 Literaturangaben.
Abstract (Originalsprache)
High voltage power transformer bushings (230 kV and above) are a known seismic vulnerability, often failing during significant earthquakes and causing potential disruption to the power supply. This occurs most commonly when the dynamic resonance between the transformer tank and the mounted bushing causes excessive amplification of the seismic demands to the bushing, leading to failure. This study evaluates multiple existing transformer designs that include stiffness discontinuities near the foundation, and the impact on the system dynamic response that results from mitigating these discontinuities with simple and potentially retrofittable blocking below the tank corners. The results of the study show that modifying the transformer bases to have an increased stiffness between the foundation and transformer tank causes a reduction in seismic high voltage bushing stress—with an average reduction of 37%.
Zitieren
APA
Bender, J., Bolisetti, C., Vaagensmith, B. C., & McKee, A. (2026). The Impact of High Voltage Power Transformer Base Design on Bushing Seismic Amplification. Earthquake Engineering & Structural Dynamics, 55(10), 2396-2408. https://doi.org/10.1002/eqe.70177
Vancouver
Bender J, Bolisetti C, Vaagensmith BC, McKee A. The Impact of High Voltage Power Transformer Base Design on Bushing Seismic Amplification. Earthquake Engineering & Structural Dynamics. 2026;55(10):2396-2408. doi:10.1002/eqe.70177
BibTeX
@article{Bender2026,
author = {Bender, Jon and Bolisetti, Chandrakanth and Vaagensmith, Bjorn C. and McKee, Aisha},
title = {The Impact of High Voltage Power Transformer Base Design on Bushing Seismic Amplification},
journal = {Earthquake Engineering & Structural Dynamics},
year = {2026},
volume = {55},
number = {10},
pages = {2396--2408},
doi = {10.1002/eqe.70177}
}
EUVIMED