Insulation failure mapping on power transformer bushing using FRA and electrostatic simulation

Salem Mgammal Al-Ameri, Waleed M Hamanah iD, Ali Ahmed Salem, Mohd Fairouz Yousof iD, Samir Ahmed Al-Gailani iD, A Abu-Siada iD

PLOS One · 07.07.2026 · 21 (7) · e0353356

DOI: 10.1371/journal.pone.0353356 ↗

Kurz gefasst

Fachartikel in der Zeitschrift PLOS One, online erschienen am 07.07.2026. Verfasst von Salem Mgammal Al-Ameri und 5 weiteren Autor:innen. Beteiligte Einrichtung: Interdisciplinary Research Center for Sustainable Energy Systems, King Fahd University of Petroleum and Minerals, Dhahran, Saudi Arabia. Hauptthemen laut MEDLINE: Static Electricity, Electric Power Supplies, Equipment Failure Analysis. Die Arbeit nennt 21 Literaturangaben. Der Volltext ist frei zugänglich (Open Access, CC BY 4.0).

AbstractSchlagwörterBibliografische AngabenZitierenVerwandte Studien

Abstract (Originalsprache)

The power transformer bushing is a critical insulation component and a frequent contributor to transformer failures. This paper presents combined electrical and Multiphysics approaches for mapping failure mechanisms in Resin-Impregnated Paper (RIP) transformer bushings using frequency response analysis (FRA) and electrostatic analysis. An 11 kV/0.433 kV, 500 kVA power transformer bushing is selected as a case study and modeled using a MATLAB-based equivalent circuit to simulate its FRA characteristics. Variations in bushing circuit capacitance are introduced to represent insulation degradation, surface pollution, and insulator damage, and the corresponding failure modes are mapped through their distinctive FRA signatures. To provide physical insight into these failure mechanisms, a detailed model is developed in COMSOL Multiphysics, where degradation, pollution, and destructive damage are analyzed using electric field and electric potential distributions. The results from the FRA simulation and electrical Multiphysics in this paper provide a framework for understanding the behavior of transformer bushing failures and enable early fault detection. This also improves the transformer bushing maintenance and condition monitoring.

Schlagwörter

MeSH-Schlagwörter (MEDLINE)

Static ElectricityElectric Power SuppliesEquipment Failure AnalysisComputer SimulationModels, TheoreticalEquipment Failure

Autor:innen und Institutionen

  • Interdisciplinary Research Center for Sustainable Energy Systems, King Fahd University of Petroleum and Minerals, Dhahran, Saudi Arabia.
  • Department of Electrical Power Engineering, Faculty of Electrical and Electronic Engineering, University Tun Hussein Onn Malaysia, Batu Pahat, Johor, Malaysia.
  • Department of Electrical Engineering, Faculty of Engineering, Aden University, Aden, Yemen.
  • Electrical and Computer Engineering Discipline, Curtin University, Bentley, Western Australia, Australia.

ORCID-Profile: Waleed M Hamanah, Mohd Fairouz Yousof, Samir Ahmed Al-Gailani, A Abu-Siada

Zitieren

APA

Al-Ameri, S. M., Hamanah, W. M., Salem, A. A., Yousof, M. F., Ahmed Al-Gailani, S., & Abu-Siada, A. (2026). Insulation failure mapping on power transformer bushing using FRA and electrostatic simulation. PLOS One, 21(7), e0353356. https://doi.org/10.1371/journal.pone.0353356

Vancouver

Al-Ameri SM, Hamanah WM, Salem AA, Yousof MF, Ahmed Al-Gailani S, Abu-Siada A. Insulation failure mapping on power transformer bushing using FRA and electrostatic simulation. PLOS One. 2026;21(7):e0353356. doi:10.1371/journal.pone.0353356

BibTeX
@article{AlAmeri2026,
  author = {Al-Ameri, Salem Mgammal and Hamanah, Waleed M and Salem, Ali Ahmed and Yousof, Mohd Fairouz and Ahmed Al-Gailani, Samir and Abu-Siada, A},
  title = {Insulation failure mapping on power transformer bushing using FRA and electrostatic simulation},
  journal = {PLOS One},
  year = {2026},
  volume = {21},
  number = {7},
  pages = {e0353356},
  doi = {10.1371/journal.pone.0353356}
}
Kostenlos starten →